| 2017-11-06 14:12:47 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE 20 AMP CIRCUIT FOR BATHROOM GFCI RECEPTACLE |
| | OUTLETS. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT |
| | SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | FBC RE3703.4 |
| | 2. WATER HEATER SHOULD BE ON A 25 AMP BREAKER. PROVIDE |
| | CORRECTION. BREAKER SHOULD BE SIZED AT 125% OF THE |
| | LOAD. PROVIDE CORRECTION. NEC 422.13; FBC RE3702.10 |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 4. PROVIDE EVIDENCE OF RESISTANCE TO GROUND ROD OF 25 |
| | OHMS OR LESS PER CODE, OR PROVIDE ADDITIONAL ELECTRODE |
| | 6 FEET AWAY. NEC 250.56; FBC RE 36008.4 |
| | 5. CONNECT TO ALL AVAILABLE GROUNDING ELECTRODES, |
| | INCLUDING THE CONCRETE ENCASED ELECTRODE. PROVIDE |
| | CORRECTION. NEC 250.50; FBC RE 3608.1 |
| | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC CE R404.1 |
| | 7. PROVIDE COMPLIANCE: "ALL 120-VOLT, SINGLE PHASE, 15 |
| | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION". A NOTE WILL |
| | SUFFICE. NEC 210.12; FBC RE3902.12 |
| | 8. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 9. ALL OUTSIDE RECEPTACLES REQUIRE GFCI PROTECTION, |
| | INCLUDING RECEPTACLES IS SOFFIT. THE GFCI DEVICE FOR |
| | RECEPTACLES IN SOFFIT SHALL BE IN A READILY ACCESSIBLE |
| | LOCATION. PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.3 |
| | 10. SMOKE/CO ALARM REQUIRED ON EACH LEVEL OF DWELLING |
| | UNIT. PROVIDE CORRECTION. ALSO, PROVIDE SMOKE ALARM FOR |
| | DEN, WHICH HAS A CLOSET AND COULD BE USED FOR SLEEPING |
| | PURPOSE. FBC RE 314.3 |
| | 11. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER |
| | SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| | IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS |
| | CODE IN SOME AREAS. PROVIDE CORRECTION. NEC |
| | 210.52(C)(1); FBC RE3901.4 |
| | 12. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS |
| | REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE |
| | CORRECTION FOR POWDER BATH. NEC 210.11(C)(3), |
| | 210.52(D); FBC RE 3703.4, 3901.6 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |