Plan Review Notes
Plan Review Notes For Permit 17100284
Permit Number 17100284
Review Stop E
Sequence Number 1
Notes
Date Text
2017-11-06 14:12:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE 20 AMP CIRCUIT FOR BATHROOM GFCI RECEPTACLE
 OUTLETS. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 FBC RE3703.4
 2. WATER HEATER SHOULD BE ON A 25 AMP BREAKER. PROVIDE
 CORRECTION. BREAKER SHOULD BE SIZED AT 125% OF THE
 LOAD. PROVIDE CORRECTION. NEC 422.13; FBC RE3702.10
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 4. PROVIDE EVIDENCE OF RESISTANCE TO GROUND ROD OF 25
 OHMS OR LESS PER CODE, OR PROVIDE ADDITIONAL ELECTRODE
 6 FEET AWAY. NEC 250.56; FBC RE 36008.4
 5. CONNECT TO ALL AVAILABLE GROUNDING ELECTRODES,
 INCLUDING THE CONCRETE ENCASED ELECTRODE. PROVIDE
 CORRECTION. NEC 250.50; FBC RE 3608.1
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 7. PROVIDE COMPLIANCE: "ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION". A NOTE WILL
 SUFFICE. NEC 210.12; FBC RE3902.12
 8. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 9. ALL OUTSIDE RECEPTACLES REQUIRE GFCI PROTECTION,
 INCLUDING RECEPTACLES IS SOFFIT. THE GFCI DEVICE FOR
 RECEPTACLES IN SOFFIT SHALL BE IN A READILY ACCESSIBLE
 LOCATION. PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.3
 10. SMOKE/CO ALARM REQUIRED ON EACH LEVEL OF DWELLING
 UNIT. PROVIDE CORRECTION. ALSO, PROVIDE SMOKE ALARM FOR
 DEN, WHICH HAS A CLOSET AND COULD BE USED FOR SLEEPING
 PURPOSE. FBC RE 314.3
 11. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE3901.4
 12. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION FOR POWDER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE 3703.4, 3901.6
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  