2017-11-07 18:38:25NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE LAND DEVELOPMENT CODE.
  
 2- GENERAL CONTRACTOR CAN NOT DO THE METAL ROOFING.
 SEC. 489.113(3) FLORIDA STATUTE. GENERAL CONTRACTOR
 NEEDS TO SUBCONTRACT THE METAL ROOFING WORK TO A
 LICENSED ROOFING CONTRACTOR. SEPARATE ROOFING PERMIT
 APPLICATION NEEDS TO BE FILL UP BY THE LICENSED ROOFING
 CONTRACTOR.
  
 3- ENTRY DOOR SIZE (2480) SPECIFIED ON THE 1ST FLOOR
 PLAN ON SHEET A1.1 DOESN'T COMPLY WITH SEC. R311.2
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED.
  
 4- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
  
 5- SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 6- SPECIFY THE SIZE OF THE ATTIC ACCESS SHOWN ON THE
 SECOND FLOOR PLAN ON SHEET A1.1. SEC. R807
 FBC-RESIDENTIAL.
  
 7- THE SIZE OF THE BATHROOM DOOR ON THE FIRST FLOOR
 DOESN'T PROVIDE A CLEAR DOOR OPENING OF 29" AS REQUIRED
 BY SEC. R320 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 8- PROVIDE DETAILS AND SPECIFICATIONS FOR STAIRWAY
 FIREBLOCKING AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 9- PROVIDE DETAILS AND SPECIFICATIONS FOR DRAFSTOPPING
 ON THE SECOND FLOOR FRAMING PLAN AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 10- CLARIFY WINDOW "F" SHOWN ON THE FLOOR PLANS. THERE
 IS NOT WINDOW "F" ON THE WINDOW ELEVATION SCHEDULE ON
 SHEET A2.2. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 11- PROVIDE COMPLETE GABLE END DETAIL COMPLYING WITH
 SEC. R609.4 FBC-RESIDENTIAL. SPECIFY ALL FRAMING
 MEMBERS, INCLUDING TOP AND BOTTOM PLATES AND ALL
 CONNECTORS.
  
 12- WOOD FRAMED GABLE END:
 A) SPECIFY THE TWO LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.6.3 FBC-RESIDENTIAL.
  
 B) ARCHITECT IS DESIGNING AN UNVENTED ATTIC, THEREFORE
 NEEDS TO SPECIFY THE WALL INSULATION OF THE GABLE END
 WALL. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 13- A) ARCHITECT IS DESIGNING AN UNVENTED ATTIC.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS ON PLANS
 SHOWING COMPLIANCE WITH THE REQUIREMENTS OF SEC. R806.5
 FBC-RESIDENTIAL.
  
 B) PROVIDE ICC EVALUATION REPORT FOR INSULATION
 SPECIFIED FOR THE UNVENTED ATTIC TO VERIFY COMPLIANCE
 WITH SEC. R806.5 AND SEC. R302.10 FBC-RESIDENTIAL.
  
 14-SECOND FLOOR FRAMING PLAN ON SHEET S1: SPECIFY HOW
 MUCH EMBEDMENT IS REQUIRED FOR THE ANCHOR BOLTS
 SPECIFIED FOR THE STRUCTURAL WOOD LEDGER SUPPORTING THE
 SECOND FLOOR TRUSSES. SEC. R301.1 FBC-RESIDENTIAL.
  
 15- FOUNDATION SCHEDULE ON SHEET S2 IS MISSING FOOTING
 F3 SHOWN ON 1ST FLOOR FRAMING ON SHEET S1. SEC. R301.1
 FBC-RESIDENTIAL.
  
 16- COVER ENTRY AND REAR OUTDOOR COVERED PATIO 1ST
 FLOOR FRAMING PLAN ON SHEET S1 SPECIFIES "DC-1" BY THE
 COLUMNS. IT IS NOT CLEAR WHAT'S DOES "DC-1" STAND FOR.
 CLARIFY AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 17- BEAM SCHEDULE ON SHEET S2 IS MISSING THE "CB-1"
 BEAM SPECIFIED ON THE ENTRY ROOF FRAMING PLAN ON SHEET
 S1. SEC. R301.1 FBC-RESIDENTIAL.
  
 18- LEFT SIDE ELEVATION ON SHEET A3.1 IS NOT THE EAST
 ELEVATION. IT IS THE WEST ELEVATION. AND, RIGHT SIDE
 ELEVATION ON SHEET A3.2 IS NOT THE WEST ELEVATION. IT'S
 THE EAST ELEVATION. REVISE AS REQUIRED MATCH PLANS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 19- SIZE OF FOOTING F-2 SPECIFIED ON THE FOOTING
 SCHEDULE ON SHEET S2 DOESN'T MATCH SIZE REPRESENTED ON
 THE 1ST FRAMING PLAN ON SHEET S1. REVISE AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 20- SIZE OF FOOTING F-4 AND F-5 SPECIFIED ON THE
 FOOTING SCHEDULE ON SHEET S2 DOESN'T MATCH SIZE
 REPRESENTED ON 1ST FRAMING PLAN ON SHEET S1 AND IS NOT
 CLEAR. IS THIS A CONCRETE PAD OR A CONTINUOUS FOOTING.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 21- STRUCTURAL NOTES, WIND DESIGN CHART AND TRUSS
 DESIGN CRITERIA ON SHEET S2 ARE REFERENCING ASCE 7-16.
 THE CURRENT ASCE 7 EDITION ADOPTED WITH THE 2014 FBC IS
 THE ASCE 7-10 NOT ASCE 7-16. REVISE AS REQUIRED BY
 CHAPTER 46 FBC-RESIDENTIAL.
  
 22- REVISE ENERGY CALCULATIONS FORM R405-2014
 SUBMITTED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER (604700). SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 DOESN'T
 MATCH CONDITIONED AREA SHOWN ON ARCHITECTURAL PLANS.
 REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C) WALL TYPES ON ITEM #9 NEED TO INCLUDE THE FRAMED
 WALL INFORMATION OF THE GABLE END AREAS. SEE
 ARCHITECT'S REVISED PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) CEILING INSULATION AND AREA SHOWN ON ITEM #10 DON'T
 MATCH PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) SPACES INFORMATION ON PAGE 2 OF 4 IS INCORRECT AND
 INCOMPLETE. REVISE THE AREA OF EACH FLOOR. WHY THERE IS
 NOT KITCHEN ON THE FIRST FLOOR?, SPECIFY THE NUMBER OF
 BEDROOMS. SPECIFY NUMBER OF OCCUPANTS BASED ON THE
 NUMBER OF BEDROOMS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 F) ROOF INFORMATION ON PAGE 2 OF 4 IS INCORRECT. REVISE
 AS REQUIRED TO MATCH PLANS. THE TYPE OF ROOF IS GABLE
 NOT HIP AND THE ROOF MATERIAL IS METAL ROOF NOT
 SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE WITH ARCHITECT AND CONTRACTOR TO AVOID
 CONFLICTS/DELAYS. SEE ITEM #23 BELOW.
  
 G) THE CEILING R-VALUE AND AREA SPECIFIED ON PAGE 2 OF
 4 DON'T MATCH PLANS. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) THE WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. REVISE AS
 REQUIRED TO MATCH. REVISE THE WINDOWS ORIENTATION,
 WINDOWS AREA AND WINDOWS OVERHANG DEPTH AND SEPARATION
 TO MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 I) PROVIDE THE COMPLETE INSPECTION CHECKLIST REQUIRED
 BY SEC. R405.4.2 (2) FBC-ENERGY CONSERVATION.
  
 J) PROVIDE THE COMPLETE EPL DISPLAY CARD SIGNED BY THE
 BUILDER AS REQUIRED BY SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 23- IT IS NOT CLEAR WHAT TYPE OF ROOFING MATERIAL IS
 GOING TO BE USED. PLANS CALL FOR METAL ROOFING, WHILE
 PRODUCT APPROVAL SUBMITTED IS FOR SHINGLES. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 24- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF MATERIAL TO BE USED. COORDINATE WITH ITEM #23
 ABOVE TO AVOID CONFLICTS/DELAYS.
  
 B) IF USING SHINGLES, THEN THE RIDGE CAP SHINGLES NOA
 13-0306.08 SUBMITTED EXPIRED ON 10/17/17. PROVIDE
 CURRENT NOA.
  
 C) ENTRY DOOR AS SHOWN ON PLANS. PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO DRAWINGS
 ET0003 SUBMITTED. NOTE: IF THERE IS NOT FLORIDA PRODUCT
 APPROVAL, THEN MANUFACTURER MAY SUBMIT COMPLETE
 ORIGINAL ENGINEER DRAWINGS FOR BUILDING OFFICIAL
 APPROVAL. CONTACT ME FOR MORE INFORMATION.
  
 D) ROUND WINDOWS AS SHOWN ON PLANS.
  
 E) WINDOW MULLIONS AS SPECIFIED ON PLANS. AND, CLEARLY
 IDENTIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 F) BALCONY UNDERLAYMENT SPECIFIED ON PLANS. NOTE: NEED
 PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE TILE AS
 SPECIFIED ON PLANS. CLEARLY IDENTIFY SPECIFIC ASSEMBLY
 TO BE USED. IF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS WILL BE REQUIRED.
  
 G) PRECAST LINTEL AS SPECIFIED ON PLANS.
  
 25- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 **** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT ALL DRAWINGS
 FOR REFERENCE.
  