| 2017-11-03 18:32:21 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PERMIT (#06050833) FOR THE ADDITION TO THE REAR |
| | OF THE STRUCTURE EXPIRED PRIOR TO RECEIVING ALL OF THE |
| | REQUIRED INSPECTIONS. |
| | PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY |
| | COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR |
| | INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL |
| | CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 |
| | & FBC 117. |
| | FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A |
| | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| | PURPOSES UNTIL APPROVED. |
| | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| | |
| | 2) OBTAIN A SET OF THE APPROVED PLANS THAT EXPIRED |
| | (PERMIT #06050833) AND SUBMIT THEM WITH THE NEW PLANS |
| | FOR REFERENCE AND TO AID THE INSPECTORS WITH THEIR |
| | FIELD INSPECTIONS. FBC 107.2.1.3 (CONTACT CRAIG |
| | MCPHERSON AT 561-805-6684 OR [email protected] TO |
| | OBTAIN COPIES FROM OUR FILES.) |
| | |
| | 3) SUBMIT A SET OF THE APPROVED PRODUCT APPROVALS FOR |
| | THE EXPIRED PERMIT AND SUBMIT THEM FOR REFERENCE AND TO |
| | AID THE INSPECTORS WITH THEIR FIELD INSPECTIONS. FBC |
| | 107.2.1.3 |
| | |
| | 4) SPECIFY THE ATTACHEMENT OF THE 4 X 6 WOOD POSTS TO |
| | THE GLULAM BEAM IN THE DETAIL ON 4.1. FBC-R 301.1 |
| | |
| | 5) THE NOTES FOR THE UPTURN BEAM ON SHEETS 2.1 AND 3.1 |
| | STATE, "SEE DETAIL THIS SHEET.". THERE IS NO DETAIL FOR |
| | THE UPTURN BEAM ON THESE SHEETS. PLEASE CORRECT. FBC |
| | 107.2.1 |
| | |
| | 6) REVISE THE TYPICAL WALL SECTION ON SHEET 4.1 TO |
| | SPECIFY 8D RING SHANK NAILS PER FBC-R 803.2.3.1. |
| | |
| | 7) REVISE THE TYPICAL WALL SECTION ON SHEET 4.1 TO |
| | SPECIFY A DOUBLE LAYER OF UNDERLAYMENT AS REQUIRED BY |
| | FBC-R 905.2.2 FOR ROOF SLOPES LESS THAN 4:12. |
| | |
| | 8) SHOW COMPLIANCE WITH FBC-R 314.3.1 WHEN ALTERATIONS, |
| | REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN |
| | ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN |
| | EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL |
| | BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR |
| | NEW DWELLINGS. |
| | |
| | |
| | |
| | |
| | |