| Plan Review Notes For Permit 17100262 |
| Permit Number |
17100262 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-10-18 14:20:46 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17100262 | | | 10/18/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED ENERGY FORM R402-2014 IS NOT FILLED | | | OUT CORRECTLY. PLEASE SEE THE SCOPE AT THE TOP OF THE | | | FORM WHERE IT STATES "TO COMPLY, A BUILDING MUST MEET | | | OR EXCEED ALL OF THE ENERGY EFFICIENCY REQUIREMENTS ON | | | TABLE 402A....." THE SUBMITTED TABLE R402A IS | | | "EXISTING" WHERE ACTUAL VALUES MUST BE FILLED IN. | | | PLEASE NOTE THE SCOPE INDICATES OTHER METHODS OF | | | COMPLIANCE IF NECESSARY WHICH INCLUDES USING THE | | | ENERGYGAUGE PERFORMANCE BASED METHOD UNDER SECTION | | | R405. PLEASE PROVIDE TWO SETS OF REVISED COMPLIANCE | | | FORMS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|