Plan Review Notes
Plan Review Notes For Permit 17100260
Permit Number 17100260
Review Stop B
Sequence Number 3
Notes
Date Text
2018-01-22 14:19:52****PROVISO****
 ****ISSUED AT APPLICANT'S RISK****
 ****ROLLUP DOORS NOT ACCEPTED AS "ACCESSIBLE" AT THIS
 TIME DUE TO LACK OF INFORMATION****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 REVISION REQUIRED; PROVIDE DETAILS TO SHOW COMPLIANCE
 WITH FBC A 404. ROLLUP DOORS ARE PROPOSED AS ACCESSIBLE
 DOORS; IT IS NOT CLEAR HOW THEY MEET ALL REQUIREMENTS
 OF FBC A 404.
  
 SOME INFORMATION WAS PROVIDED, BUT SPEC SHEET REFERS TO
 "ADA CODE" AND SECTIONS WHICH DO NOT CORRELATE WITH THE
 FLORIDA BUILDING CODE. THIS INFORMATION IS REQUIRED FOR
 CONSIDERATION BY THE BUILDING OFFICIAL.
  
  
  
  