Plan Review Notes
Plan Review Notes For Permit 17100260
Permit Number 17100260
Review Stop M
Sequence Number 2
Notes
Date Text
2017-12-27 08:37:391ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #17100260
 12/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST FOR AN ENERGY COMPLIANCE SUBMITTAL.
  
 2) THE AC CALCULATIONS INDICATE THE 3.5 TON SYSTEMS ARE
 OVERSIZED- SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 3) M-1: INDICATE THE TYPE OF OUTDOOR AIR DUCTWORK TO BE
 INSTALLED PER SECTION 603. THE PLAN IS INDICATING AN 8"
 PIPE.
  
 4) M-1: PROVIDE AN AIR HANDLER INSTALLATION DETAIL-
 SECTION 304.1.
  