| 2017-12-27 08:37:39 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | PERMIT #17100260 | | | 12/27/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) 2ND REQUEST FOR AN ENERGY COMPLIANCE SUBMITTAL. | | | | | | 2) THE AC CALCULATIONS INDICATE THE 3.5 TON SYSTEMS ARE | | | OVERSIZED- SECTION C403.2.2 FBC-14 ENERGY CONSERVATION. | | | | | | 3) M-1: INDICATE THE TYPE OF OUTDOOR AIR DUCTWORK TO BE | | | INSTALLED PER SECTION 603. THE PLAN IS INDICATING AN 8" | | | PIPE. | | | | | | 4) M-1: PROVIDE AN AIR HANDLER INSTALLATION DETAIL- | | | SECTION 304.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|