| 2017-10-24 16:54:43 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, |
| | EXISTING BUILDING CODES. |
| | PERMIT #17100260 |
| | 10/24/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE PROPOSED PROJECT INCLUDES ADDING NEW AC SYSTEMS TO |
| | DEAD STORAGE SPACE. THESE NEW SYSTEMS ARE NOT |
| | "CHANGE-OUTS" CONTRARY TO THE ARCHITECT'S NOTE ON SHEET |
| | A-1. THERE ARE NO BUILDING DEPARTMENT RECORDS OF ANY |
| | LEGALLY PERMITTED AC SYSTEMS IN THE SPACE. MECHANICAL |
| | PLANS ARE REQUIRED WITH THIS SUBMITTAL- SEE COMMENTS |
| | BELOW. |
| | |
| | 1) THE PREVIOUSLY UNCONDITIONED STORAGE SPACE NOW BEING |
| | CONDITIONED SHALL BE BROUGHT INTO FULL COMPLIANCE WITH |
| | THE FBC-14 ENERGY CONSERVATION CODE- SEE SECTION |
| | C101.4.5. PLEASE PROVIDE AN ENERGY COMPLIANCE SUBMITTAL |
| | USING ONE OF THE METHODS LISTED UNDER SECTION C401.2. |
| | |
| | 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. |
| | |
| | 3) INDICATE HOW FRESH AIR WILL BE PROVIDED TO THE SPACE |
| | USING EITHER NATURAL OR MECHANICAL VENTILATION- SEE |
| | SECTIONS 402 AND 403 AND PROVIDE CALCULATIONS. |
| | |
| | 4) IF MECHANICAL VENTILATION IS TO BE PROVIDED, SHOW |
| | THE LOCATIONS OF THE O/A DUCTS AND PROVIDE DETAILS- |
| | TYPES AND SIZES OF DUCTS, INLET LOCATIONS AND CLEARANCE |
| | DISTANCES, TYPES OF SHUTOFF DAMPERS AND LOCATIONS. |
| | |
| | 5) PROVIDE AC LAYOUT PLANS INCLUDING A DUCT LAYOUT AND |
| | EQUIPMENT SCHEDULES. SHOW THE CFMS AT EACH SUPPLY |
| | DIFFUSER AND RETURN GRILL. |
| | |
| | 6) PROVIDE AN AIR DISTRIBUTION SCHEDULE. |
| | |
| | 7) PROVIDE CONDENSATE DISPOSAL PLANS. |
| | |
| | 8) PROVIDE WIND LOAD ENGINEERING FOR CONSTRUCTION OF |
| | THE CONDENSER PADS AND TIE DOWN OF THE CONDENSERS TO |
| | THE PADS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |