| Date |
Text |
| 2018-01-31 16:57:56 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH |
| | |
| | 3. SHT. A-202 DETAIL #3 THE WATER CLOSET DIMENSION OFF |
| | THE SIDE WALL SHALL BE 16" MIN. AND 18" MAX. PER FBC |
| | ACC 604.2 |
| | |
| | 7. SHT. A-401 THE ROOF DRAIN ISOMETRIC SHOWS THE |
| | HORIZONTAL PIPING RUN AT 1/8" PER FT PER TABLE 1106.3 |
| | 4" AT 1/8" PER FT IS 1504 SQFT MAX . THE LAST SECTION |
| | OF HORIZONTAL PIPING SHALL BE 5" MIN OR RUN AT 1/4" PER |
| | FT PLEASE CORRECT PLAN PER FBC PL TABLE 1106.3 |
| | |
| | 8. SHT. A-402 PROVIDE DETAIL THAT SHOWS THE DIMENSIONS |
| | OF THE OVERFLOW SCUPPER SIZED PER FBC PL TABLE 1106.7 |
| | SHOW COMPLIANCE WITH FBC 1503.4.2.1 |
| | |
| | 9. A SEPARATE PERMIT IS REQUIRED FOR BACKFLOW PER WPB |
| | UTILITIES DEPT. PLEASE PROVIDE NOTE ON PLAN. |
| | |
| | 10. PLEASE SHOW COMPLIANCE WITH FBC PL 416.5 TEMPERED |
| | WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 12. HOT WATER IS REQUIRED AT SERVICE SINK PER FBC PL |
| | 607.1 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SERVICE SINK NOT SHOWN ON PLUMBING RISERS. CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |