| 2017-11-04 11:44:42 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A-202 DETAIL #1 IT APPEARS THE CLEAR FLOOR |
| | SPACE FOR THE FIXTURES IS BEING SHOWN OUTSIDE THE |
| | BATHROOM. PLEASE SHOW THE FIXTURES INSIDE THE REQUIRED |
| | CLEAR FLOOR SPACE AND PROVIDE DIMENSIONS ON FLOOR |
| | SPACE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 |
| | DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| | DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS |
| | DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | 3. SHT. A-202 DETAIL #3 THE WATER CLOSET DIMENSION OFF |
| | THE SIDE WALL SHALL BE 16" MIN. AND 18" MAX. PER FBC |
| | ACC 604.2 |
| | |
| | 4. A-201 UNDER APPLICABLE CODE IT LIST THE EXISTING |
| | BUILDING CODE AND CHANGE OF USE THE PLAN CALLS IT A NEW |
| | WAREHOUSE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHT. A-401 THE ROOF DRAIN CALCULATIONS LIST A MAIN |
| | HOUSE AND GUEST HOUSE WITH DIFFERENT SQFT THAN THE ROOF |
| | PLAN SHOWS PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. THE PERMIT APPLICATION SHOWS UNDER WORK DESCRIPTION |
| | A NEW SFR PLEASE CLARIFY AND CORRECT APPLICATION. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. SHT. A-401 THE ROOF DRAIN ISOMETRIC SHOWS THE |
| | HORIZONTAL PIPING RUN AT 1/8" PER FT PER TABLE 1106.3 |
| | 4" AT 1/8" PER FT IS 1800 SQFT MAX . THE LAST SECTION |
| | OF HORIZONTAL PIPING SHALL BE 5" MIN OR RUN AT 1/4" PER |
| | FT PLEASE CORRECT PLAN PER FBC PL TABLE 1106.3 |
| | |
| | 8. SHT. A-402 PROVIDE DETAIL THAT SHOWS THE DIMENSIONS |
| | OF THE OVERFLOW SCUPPER SIZED PER FBC PL TABLE 1106.7 |
| | |
| | 9. A SEPARATE PERMIT IS REQUIRED FOR BACKFLOW PER WPB |
| | UTILITIES DEPT. PLEASE PROVIDE NOTE ON PLAN. |
| | |
| | 10. PLEASE SHOW COMPLIANCE WITH FBC PL 416.5 TEMPERED |
| | WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 11. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1 |
| | |
| | 12. HOT WATER IS REQUIRED AT SERVICE SINK PER FBC PL |
| | 607.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |