| 2017-11-07 10:12:35 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17100244 |
| | 11/7/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | PLEASE ADDRESS THE FOLLOWING COMMENTS. |
| | |
| | 1) SHEET A-201: REFER TO BUILDING REVIEW COMMENTS AND |
| | ADDRESS THE DISCREPANCIES IN THE BUILDING CODE AND |
| | DESIGN ANALYSIS. THE DESCRIPTION OF WORK IS INDICATING |
| | A NEW RESTAURANT TO BE BUILT-OUT IN A VACANT SPACE, |
| | HOWEVER THIS IS A NEW BUILDING THAT YOU ARE CLASSIFYING |
| | AS A STORAGE/WAREHOUSE. A THOROUGH MECHANICAL REVIEW |
| | CANNOT BE COMPLETED AT THIS TIME. |
| | |
| | 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | 5-TON AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY |
| | CONSERVATION AND SECTION 312.1 FBC-14 MECHANICAL. |
| | |
| | 3) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH |
| | THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS |
| | C101.5 AND C401.2 AND SUBMIT AN ENERGY COMPLIANCE |
| | REPORT. |
| | |
| | 4) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 5) INDICATE HOW OUTDOOR AIR IS BEING PROVIDED TO THE |
| | NEW AIR HANDLER, AND COMPLY WITH SECTION C403.2.4.4. |
| | FOR REQUIRED DAMPER. |
| | |
| | 6) SHEETS A-501 & A-502: KEY NOTE #1 NOT SHOWN ON THE |
| | PLAN. PLEASE SHOW THE CONDENSATE PIPING RUN AND |
| | DISPOSAL LOCATION. |
| | |
| | 7) A-501 & A-502: A SMOKE DETECTOR IS REQUIRED IN THE |
| | RETURN AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION |
| | 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED |
| | IF THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS |
| | ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY |
| | AIR, HOWEVER HE PLAN IS INDICATING 2320 CFMS OF SUPPLY |
| | AIR. |
| | |
| | 8) A-501 & A-502: PROVIDE AN AIR DEVICE SCHEDULE TO |
| | MATCH THE SYMBOLS ON THE PLAN. |
| | |
| | 9) A-501 & A-502: SHOW THE BATH EXHAUST DUCT RUN AND |
| | TERMINATION LOCATION AND A TERMINATION CAP DETAIL. |
| | |
| | 9) ADVISORY: A NON-COMBUSTIBLE DOOR FOR THE AC CLOSET |
| | WILL BE REQUIRED IF THE RETURN IS NOT DUCTED DIRECTLY |
| | TO THE AIR HANDLER- SEE SECTION C403.2.7.2 FBC-14 |
| | ENERGY CONSERVATION CODE, AND SECTION 602.2.1 FBC-14 |
| | MECHANICAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |