| Plan Review Notes For Permit 17100210 |
| Permit Number |
17100210 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-31 11:53:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET 101.08 - THE CLOSET DIMENSIONS, 5' 1/2" X 2' 5 | | | 5/8" INDICATE AN AREA GREATER THAN 12SQ/FT. SHEET | | | 606.08 DOES NOT SHOW A SPRINKLER HEAD PROTECTING THE | | | CLOSET. | | | | | | PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS. | | | | | | 30.3.5.3* IN BUILDINGS SPRINKLERED IN ACCORDANCE WITH | | | NFPA 13, | | | STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, | | | CLOSETS LESS | | | THAN 12 FT2 (1.1 M2) IN AREA IN INDIVIDUAL DWELLING | | | UNITS SHALL NOT | | | BE REQUIRED TO BE SPRINKLERED. CLOSETS THAT CONTAIN | | | EQUIPMENT SUCH | | | AS WASHERS, DRYERS, FURNACES, OR WATER HEATERS SHALL BE | | | SPRINKLERED, | | | REGARDLESS OF SIZE. | | | | | | PLEASE JUSTIFY OR PROVIDE SPRINKLER COVERAGE IN THIS | | | CLOSET. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|