Plan Review Notes
Plan Review Notes For Permit 17100210
Permit Number 17100210
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-10-31 11:53:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 101.08 - THE CLOSET DIMENSIONS, 5' 1/2" X 2' 5
 5/8" INDICATE AN AREA GREATER THAN 12SQ/FT. SHEET
 606.08 DOES NOT SHOW A SPRINKLER HEAD PROTECTING THE
 CLOSET.
  
 PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS.
  
 30.3.5.3* IN BUILDINGS SPRINKLERED IN ACCORDANCE WITH
 NFPA 13,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS,
 CLOSETS LESS
 THAN 12 FT2 (1.1 M2) IN AREA IN INDIVIDUAL DWELLING
 UNITS SHALL NOT
 BE REQUIRED TO BE SPRINKLERED. CLOSETS THAT CONTAIN
 EQUIPMENT SUCH
 AS WASHERS, DRYERS, FURNACES, OR WATER HEATERS SHALL BE
 SPRINKLERED,
 REGARDLESS OF SIZE.
  
 PLEASE JUSTIFY OR PROVIDE SPRINKLER COVERAGE IN THIS
 CLOSET.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  