| 2017-11-01 12:31:54 | W. P. B. REVISION: 17100210 |
| | W. P. B. PERMIT: 15111020 |
| | ADD: 1100 S. FLAGLER DR. SUITE: GUEST UNIT: 10 |
| | CONT: SUFFOLK |
| | TEL: 561-691-4552 # 103 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | SUBJECT TO FAIR HOUSING! |
| | |
| | 1ST REVIEW |
| | DATE: WED. NOV. 01/ 2017 |
| | |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW SHEET 607.10-FP2-90-GS10 AND SHEET |
| | 103.10-A2-90-GS10 CLOSET DIMENSION OF 2 FT. 5 5/8 |
| | INCHES X 5 FOOT ? INCH OR 14.48 SQ. FT. |
| | THE 2010 FBC-B 403.3 AUTOMATIC SPRINKLER SYSTEM. |
| | BUILDINGS AND STRUCTURES SHALL BE EQUIPPED THROUGHOUT |
| | WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1. |
| | |
| | F] 903.3.1.1 NFPA 13 SPRINKLER SYSTEMS. WHERE THE |
| | PROVISIONS OF THIS CODE REQUIRE THAT A BUILDING OR |
| | PORTION THEREOF BE EQUIPPED THROUGHOUT WITH AN |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH THIS |
| | SECTION, SPRINKLERS SHALL BE INSTALLED THROUGHOUT IN |
| | ACCORDANCE WITH NFPA 13 EXCEPT AS PROVIDED IN SECTION |
| | 903.3.1.1.1 CHAPTER 30, 30.3.5.3 THE STANDARD FOR THE |
| | INSTALLATION OF SPRINKLER SYSTEMS IN CLOSETS LESS THAN |
| | 12 SQ. FT. IN AREA IN INDIVIDUAL DWELLING UNITS SHALL |
| | NOT BE REQUIRED TO BE FIRE SPRINKLERED. THIS CLOSET IS |
| | OVER 12 SQUARE FEET. L |
| | |
| | BUILDING PROVISO |
| | |
| | 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR |
| | COMPLIANCE WITH THE 2010 FBC-B SECTIONS: |
| | FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FBC-B 2010 1207.2 AIR-BORNE SOUND. |
| | FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE |
| | SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS |
| | SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE |
| | DESIGNER OF RECORD. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |