2017-10-31 15:59:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS 4/0 WIRE FOR A 350 AMP SERVICE.
 4/0 WIRE IS NOT RATED FOR A 350 AMP SERVICE. PROVIDE
 CORRECTION. FBC RE TABLE 3603.1
 2. SHEET A-12, NOTE 1 REFERENCES NEC 406.11 FOR TAMPER
 RESISTANT RECEPTACLES. THIS CODE SECTION DOES NOT APPLY
 TO TAMPER RESISTANT RECEPTACLES. PROVIDE CORRECTION.
 NEC 406.12; FBC RE4002.14
 3. SHEET A-12, NOTE 13 STATES THAT LIGHTING IN CLOTHES
 CLOSETS SHALL COMPLY WITH NEC 4/10.8/D/1, WHICH DOESN?T
 EXIST. PROVIDE CORRECTION. NEC 410.16; FBC RE4003.12
 4. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR POOL. FBC 105.1,
 107.2.1
 5. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1
 6. PROVIDE 20 AMP CIRCUIT FOR BATHROOM GFCI RECEPTACLE
 OUTLETS. FBC RE 3703.4
 7. RECEPTACLE FOR GARAGE DOOR OPENER REQUIRES GFCI
 PROTECTION. FBC RE 3902.2
 8. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 9. WATER HEATER IS STATED AS A 5000 WATT LOAD. OCP FOR
 THIS LOAD SHOULD BE CALCULATED AT 125% OF THE WATTAGE
 DIVIDED BY 240 VOLT, WHICH EQUALS 26.04 AMPS. THE NEXT
 SIZE BREAKER WOULD BE 30 AMP, NOT 40 AMP AS SHOWN IN
 PANEL SCHEDULE. PROVIDE CORRECTION. FBC RE 3702.10
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  