2017-11-15 15:21:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE EXPOSURE CATEGORY FOR THIS STRUCTURE SHOULD BE
 "C" RATHER THAN "B". FBC-R301.2.4.3
  
 2) ADJUST THE REQUIRED COMPONENT AND CLADDING PRESSURES
 TO REFLECT EXPOSURE "C" AS NECESSARY. FBC-R301.2.1
  
 3) ON SHEET A2 THE FLOOD ZONE IS SPECIFIED AS B. THE
 NEW FEMA FLOOD MAPS WERE ADOPTED BY THE CITY OF WEST
 PALM BEACH ON OCTOBER 5, 2017. THIS PROJECT FALLS UNDER
 THE PURVIEW OF THESE NEWLY ADOPTED MAPS. THEREFORE, THE
 FLOOD ZONE FOR THIS PROPERTY IS NOW "X" AND THE
 ELEVATIONS SHOULD BE IN NAVD 88 DATUM.
  
 4) THE TYPE OF CONSTRUCTION ON SHEET A2 SHOULD BE V-B
 FOR THIS STRUCTURE. FBC TABLE 601
  
 5) ON SHEET A2 THE ACI 318, 530 AND 530.1 STANDARDS
 SHOULD BE UPDATED TO THE 2011 EDITIONS PER THE
 REFERENCED STANDARDS IN CHAPTER 46 OF THE FBC-R.
  
 6) PROVIDE TWO SETS OF A SITE DRAINAGE PLAN THAT SHOWS
 COMPLIANCE WITH FBC-R401.3 DRAINAGE. SURFACE DRAINAGE
 SHALL BE DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER
 APPROVED POINT OF COLLECTION THAT DOES NOT CREATE A
 HAZARD. LOTS SHALL BE GRADED TO DRAIN SURFACE WATER
 AWAY FROM FOUNDATION WALLS. THE GRADE SHALL FALL A
 MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET
 (3048 MM). EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR
 OTHER PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF
 FALL WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL
 BE CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE
 STRUCTURE. IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM)
 OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 7) THE FIRST FLOOR PLAN ON SHEET A5 SHOWS AN ATTIC
 ACCESS AND AN AIR HANDLER IN THE ATTIC ABOVE THE
 GARAGE. THERE IS A SECOND FLOOR ABOVE THE GARAGE.
 PLEASE CORRECT. FBC 107.2.1
  
 8) SHOW COMPLIANCE WITH FBC-R 807.1 FOR ATTIC ACCESS.
  
 9) SHOW COMPLIANCE WITH FBC-R 318.5 WHICH REQUIRES
 GUTTERS WITH DOWNSPOUTS ON ALL BUILDINGS WITH EAVES OF
 LESS THAN 6 INCHES OF HORIZONTAL PROJECTION.
  
 10) THE ENERGY FORM R405-2014 IS REQUIRED TO HAVE THE
 OWNER/AGENTS SIGNATURE. FBC ENERGY CONSERVATION SECTION
 R103.1.1.2
  
 11) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE
 SECTIONAL OVERHEAD GARAGE DOOR ON THE PLANS. FBC-R
 301.2.1
  
 12) SPECIFY THE REQUIRED UPLIFT PRESSURES FOR THE FLAT
 ROOF, ZONES 1, 2 AND 3 ON THE PLANS. FBC-R 301.2.1
  
 13) THE DOOR FROM THE GARAGE TO THE RESIDENCE IS
 REQUIRED TO COMPLY WITH FBC-R 302.5.1 AND BE EQUIPPED
 WITH A SELF-CLOSING DEVICE.
  
 14) SUBMIT TWO SETS OF THE PRODUCT EVALUATIONS FOR THE
 SPRAY FOAM INSULATION. FBC-R 316
  
 15) SUBMIT TWO SETS OF THE MANUFACTURER'S
 SPECIFICATIONS AND THE INSTALLATION INSTRUCTIONS FOR
 THE BUILT IN GAS BBQ GRILL. FBC 107.2.1 & FBCR-G2404.3
  
 16) SHOP DRAWINGS FOR THE GUARDS AND RAILINGS SHALL BE
 SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO THEIR
 INSTALLATION. FBC-R 312.1
  
 17) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE STRUCTURAL
 MULLIONS, THE "SARASOTA"STORM SHUTTERS, THE SOLID CORE
 FLUSH METAL DOOR AND THE HALF LITE METAL OUTSWING DOOR.
  
 18) TWO DIFFERENT CERTAINTEED NOAS WERE SUBMITTED FOR
 THE MODIFIED ROOF SYSTEMS. IDENTIFY WHERE EACH ONE WILL
 BE USED. INDICATE THE SPECIFIC SYSTEM THAT WILL BE
 INSTALLED AND THE MAXIMUM DESIGN PRESSURE FOR IT FROM
 THE NOA. SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING OF THE PERIMETER
 AND CORNER AREAS PER LIMITATION NUMBER 7 OF THE NOA.
 FBC 107.2.1
  
 19) THE VALUATION FOR THIS PROJECT HAS BEEN INCREASED
 TO $418, 678.00 BASED ON THE LATEST ICC VALUATION DATA.
 FBC 109.3
  
 20) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  