| Plan Review Notes For Permit 17100173 |
| Permit Number |
17100173 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-05 14:49:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) IT IS INDICATED THAT CARD READERS ARE BEING | | | INSTALLED AT THE TWO SECOND FLOOR EXIT STAIRWELL DOORS. | | | | | | THESE ARE REQUIRED EXITS AND THE CARD READERS AT THESE | | | LOCATION IS A VIOLATION OF NFPA 101, CHAPTER 7, MEANS | | | OF EGRESS. | | | | | | NO APPROVED LISTED HARDWARE COMPLIANT OR INDICATIONS | | | THAT ALL 6 OF THE SUBSECTIONS ARE COMPLIANT WITH | | | SECTION 7.2.1.5.6 IS PROVIDED/SUBMITTED. | | | | | | THESE DOORS CAN NOT BE LOCKED IN THE PATH OF EGRESS | | | WITHOUT THE APPROVED LISTED HARDWARE AND ALL 6 | | | SUBSECTIONS ARE DOCUMENTED.. | | | | | | PLEASE PROVIDE HARDWARE DETAIL AND ALL 6 SUBSECTIONS | | | INFORMATION AT THESE LOCATIONS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|