| Date |
Text |
| 2017-11-02 14:23:23 | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | C405.2.4 EXTERIOR LIGHTING CONTROLS. |
| | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION |
| | SHALL BE CONTROLLED BY EITHER A COMBINATION |
| | OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL |
| | TIME SWITCH. LIGHTING DESIGNATED FOR DUSK |
| | -TO-DAWN OPERATION SHALL BE CONTROLLED BY AN |
| | ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND |
| | THE TIME SETTING DURING LOSS OF POWER |
| | FOR A PERIOD OF AT LEAST 10 HOURS. |
| | |
| | C405.6.2 EXTERIOR BUILDING LIGHTING POWER. THE TOTAL |
| | EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL |
| | EXTERIOR BUILDING APPLICATIONS IS THE SUM OF THE BASE |
| | SITE ALLOWANCE PLUS THE INDIVIDUAL ALLOWANCES |
| | FOR AREAS THAT ARE TO BE ILLUMINATED AND ARE PERMITTED |
| | IN TABLE C405.6.2(2) FOR THE APPLICABLE LIGHTING |
| | ZONE. TRADEOFFS ARE ALLOWED ONLY AMONG EXTERIOR |
| | LIGHTING APPLICATIONS LISTED IN TABLE C405.6.2(2), |
| | TRADABLE SURFACES SECTION. THE LIGHTING ZONE FOR THE |
| | BUILDING EXTERIOR IS DETERMINED FROM TABLE |
| | C405.6.2(1) UNLESS OTHERWISE SPECIFIED BY THE LOCAL |
| | JURISDICTION. EXTERIOR LIGHTING FOR ALL APPLICATIONS |
| | (EXCEPT THOSE INCLUDED IN THE EXCEPTIONS TO SECTION |
| | C405.6.2) SHALL COMPLY WITH THE REQUIREMENTS |
| | OF SECTION C405.6.1 |