| Plan Review Notes For Permit 17100128 |
| Permit Number |
17100128 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-14 06:11:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | FBC B CHAPTER 10: | | | | | | 1. SEE FIRE COMMENTS; APPLICABLE FOR BUILDING REVIEW. | | | | | | 2. APPLICANT'S NEEDS RE: PHASED TCO PLAN ARE NOT CLEAR. | | | WHAT IS THE ANTICIPATED TIMING? IT APPEARS THAT THIS | | | REQUEST IS PREMATURE. | | | | | | 3. PROVIDE A LIFE SAFETY PLAN WHICH SHOWS ACCESS TO TWO | | | REMOTELY LOCATED EXITS. | | | | | | 4. FINAL TCO PHASING APPROVAL WILL BE SUBJECT TO KEN | | | CONRAD'S APPROVAL. THIS WILL REQUIRE A WALK THROUGH | | | PRIOR TO THAT TIME, BUT AT A POINT CLOSER TO ACTUAL TCO | | | REQUEST. | | | | | | 5. PROVIDE THE DRY-IN PLAN REQUESTED BY KEN CONRAD. | | | PLEASE PROVIDE THIS ON THE JOB SITE, AND SCHEDULE AN IN | | | PROGRESS, MISCELLANEOUS, OR OTHER INSPECTION AS | | | APPLICABLE. | | | | | | | | | |
|