| Plan Review Notes For Permit 17100109 |
| Permit Number |
17100109 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-21 12:44:26 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE BRANCH DRAIN FOR KITCHEN SHALL CONNECT DOWN | | | STREAM OF THE BRANCHDRAIN FOR THE BATHROOMS IT SHALL | | | NOT CONNECT TO WATER CLOSET DRAIN. PER FBC PL P3108.1 | | | | | | 2. THE SANITARY ISOMETRIC DRAWING SHOWS A HORIZONTAL | | | DRY VENT CONNECTED AT THE SHOWER IN MASTER BATH | | | HORIZONTAL DRY VENT ARE NOT ALLOWED. PLEASE REMOVE FROM | | | FLOOR PLAN AND RISER.PER FBC PL P3104.3 AND P3104.4 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|