2017-10-21 13:22:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-101 NOTE ON HOT WATER LINE DETAIL #1 SHOWS
 HOT WATER CONNECTED TO COLD WATER PLEASE CLARIFY.PER
 WPB AMEND TO FBC 107.2.1
  
 2. SHOW DISTANCE FROM WATER HEATER IF OVER 50' A
 RECIRCULATION SYSTEM WITH INSULATED PIPING WILL BE
 REQUIRED. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  