| Plan Review Notes For Permit 17100107 |
| Permit Number |
17100107 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-22 11:40:01 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | PERMIT #17100717 | | | 11/22/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) TWO DIFFERENT SETS OF ENERGY AND AC CALCULATIONS | | | HAVE BEEN SUBMITTED EACH SPECIFYING A DIFFERENT SYSTEM | | | THAN WHAT IS SHOWN ON SHEET M101 WHICH IS A 3.0 TON | | | MITSUBISHI SYSTEM. THE CALCULATIONS ARE INDICATING | | | EITHER A 1-TON DAIKIN OR A 1-1/2 TON MITSUBISHI SYSTEM. | | | PLEASE DISCARD WHICH EVER SETS OF CALCULATIONS ARE NOT | | | RELEVANT AND CORRECT THE AC SCHEDULE ON THE PLAN TO | | | MATCH. | | | | | | 2) THE OWNER/AGENT SHALL SIGN THE ENERGY COMPLIANCE | | | FORM R405-2014- SEE SECTION R103.1.1.2 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 3) SUBMIT THE MIAMI-DADE NOA OR FLORIDA PRODUCT | | | APPROVAL FOR THE CONDENSER TIE-DOWN CLIPS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|