2017-11-22 11:40:011ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17100717
 11/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TWO DIFFERENT SETS OF ENERGY AND AC CALCULATIONS
 HAVE BEEN SUBMITTED EACH SPECIFYING A DIFFERENT SYSTEM
 THAN WHAT IS SHOWN ON SHEET M101 WHICH IS A 3.0 TON
 MITSUBISHI SYSTEM. THE CALCULATIONS ARE INDICATING
 EITHER A 1-TON DAIKIN OR A 1-1/2 TON MITSUBISHI SYSTEM.
 PLEASE DISCARD WHICH EVER SETS OF CALCULATIONS ARE NOT
 RELEVANT AND CORRECT THE AC SCHEDULE ON THE PLAN TO
 MATCH.
  
 2) THE OWNER/AGENT SHALL SIGN THE ENERGY COMPLIANCE
 FORM R405-2014- SEE SECTION R103.1.1.2 FBC-14 ENERGY
 CONSERVATION.
  
 3) SUBMIT THE MIAMI-DADE NOA OR FLORIDA PRODUCT
 APPROVAL FOR THE CONDENSER TIE-DOWN CLIPS.
  