2017-10-31 13:36:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CIRCUIT 10 IN PANEL B SHOWS A SMALL APPLIANCE
 CIRCUIT ON A 15 AMP BREAKER. PROVIDE CORRECTION. FBC RE
 3703.2
 2. PROVIDE CORRECT LOAD CALCULATION. THERE SHOULD BE
 ONE LOAD CALCULATION FOR THE ENTIRE RESIDENCE. SEE FBC
 RESIDENTIAL TABLE 3602.2 FOR PROPER FORMAT. FBC RE 3602
 3. RISER DIAGRAM SHOWS (3) 3/0 WIRES IN A 2 INCH
 CONDUIT FROM MAIN BREAKER DISCONNECT TO PANEL A.
 IDENTIFY IS THIS WIRE IS COPPER OR ALUMINUM.
 ADDITIONALLY, THERE SHOULD BE AN EGC IN THIS CONDUIT.
 THIS RUN IS ALSO IDENTIFIED AS CIRCUIT A-17,19. REMOVE
 DISCREPANCY. FBC 107.2.1; FBC RE 3704.6
 4. RISER SHOWS THE CONDUIT FROM PANEL A TO PANEL B WITH
 (4) 1/0 CONDUCTORS IN 1.5 INCH CONDUIT. PLAN SHOWS SAME
 RUN WITH (4) 1/0 CONDUCTORS WITH A # 6 EGC. IDENTIFY
 WIRE TYPE. CORRECT DISCREPANCY. WHY (4) 1/0 WIRES, THIS
 IS NOT A 3 PHASE PANEL? ALSO, (4) 1/0 WIRES WITH A # 6
 EXCEEDS THE CAPACITY OF A 1.5 INCH CONDUIT. PROVIDE
 CORRECTION. FBC 107.2.1; FBC RE 3704.6, TABLES 3904
 5. WHY DOES THE RISER SHOW A SEPARATE GROUNDING
 ELECTRODE SYSTEM AT PANEL B? IS THIS A SEPARATE
 STRUCTURE? IF NOT, THERE SHOULD ONLY BE ONE GROUNDING
 ELECTRODE SYSTEM AT THE SERVICE. IF THIS IS A SEPARATE
 STRUCTURE, PANEL B WILL REQUIRE A MAIN BREAKER. CLARIFY
 AND/OR CORRECT. FBC RE 3607.1, 3607.3; FBC 107.2.1
 6. PANEL SCHEDULE DOES NOT SHOW THE 20 AMP CIRCUIT
 REQUIRED FOR THE BATHROOM RECEPTACLE OUTLET. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE 3703.4
 7. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 8. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION.
 NEC 410.16; FBC RE4003.12
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FLOOR PLAN OF ENTIRE RESIDENCE
 SHOWING ALL EXISTING ALARMS. IF NONE ARE EXISTING OR
 NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC
 107.2.1
 10. EXTERIOR OUTLET FOR IGNITOR IS REQUIRED TO BE GFCI
 PROTECTED. PROVIDE CORRECTION. FBC RE 3902.3
 11. PROVIDE LOCATION ON PLAN OF ALL MECHANICAL
 EQUIPMENT TO BE INSTALLED AND THE ELECTRICAL
 DISCONNECTS REQUIRED. FBC 107.2.1; FBC RE 4101.5
 12. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 13. PANEL B IS SHOWN AS BEING FED FROM A 150 AMP PLUG
 IN BREAKER. NO MANUFACTURER THAT I KNOW OF MAKES A
 BREAKER THIS SIZE FOR PLUG IN USE. CLARIFY AND/OR
 CORRECT. FBC 107.2.1; NEC 110.3
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  