| Plan Review Notes For Permit 17100070 |
| Permit Number |
17100070 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-06 18:20:36 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE ROOF SLOPE, ROOF TYPE ( GABLE OR HIP ) | | | AND THE MEAN ROOF HEIGHT FOR THE STRUCTURE. FBC 107.2.1 | | | | | | 2) INDICATE THE SPECIFIC CONCRETE TILE THAT WILL BE | | | USED FROM THE ONES THAT ARE LISTED IN THE PRODUCT | | | APPROVAL. FBC 107.2.1 | | | | | | 3) SPECIFY THE TILE PROFILE AND THE PADDY SIZE AND | | | NUMBER OF PADDIES OF ADHESIVE THAT WILL BE USED FROM | | | THE AH-160 PRODUCT APPROVAL. THE ALLOWABLE OVERTURNING | | | MOMENT HAS TO BE GREATER THAN THE REQUIRED OVERTURNING | | | MOMENT FROM THE TILE PRODUCT APPROVAL. FBC 107.2.1 | | | | | | 4) THIS STRUCTURE IS LOCATED IN EXPOSURE CATEGORY D | | | WITH A 170 MPH VULT WINDSPEED. THE UPLIFT IN THE | | | CORNERS (ROOF ZONE 3) EXCEEDS THE MAXIMUM DESIGN | | | PRESSURE OF -105 PSF FOR THE CERTAINTEED W-77 ROOF | | | SYSTEM SELECTED FOR THE FLAT ROOF. FBC - R 301.2.1 | | | |
|