| 2017-10-04 11:47:59 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE CITY OF WEST PALM BEACH HAS NOT ADOPTED THE USE | | | OF RAS 150. SUBMIT SIGNED AND SEALED ENHANCED FASTENING | | | CALCULATIONS FROM A FLORIDA LICENSED ARCHITECT OR | | | ENGINEER. FBC 107.2.1.3 | | | | | | 2) THE SIGNED AND SEALED ATTACHMENT CALCULATIONS FOR | | | THE LIGHTWEIGHT CONCRETE DECK THAT WERE SUBMITTED | | | SPECIFY PRODUCT APPROVAL FL2533-R17 AND SYSTEM NUMBER | | | LWC-32. THE PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR | | | FL2533-R18 AND SYSTEM NUMBER LWC-31 WAS HI-LIGHTED AS | | | THE ONE BEING INSTALLED. IN ORDER TO AVOID MISTAKES AND | | | CONFUSION, PLEASE COORDINATE THE DOCUMENTS THAT YOU ARE | | | SUBMITTING. FBC 107.2.1 |
|