Plan Review Notes
Plan Review Notes For Permit 17100042
Permit Number 17100042
Review Stop E
Sequence Number 2
Notes
Date Text
2017-11-16 08:00:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL 2ND REVIEW STATUS: DENIED, SEE COMMENTS
 BELOW.
  
 ALL OF THE FOLLOWING COMMENTS WERE PREVIOUS COMMENTS
 THAT WERE NOT ADDRESSED. RESPONSE LETTER STATED THE
 ITEMS WERE CORRECTED ON SHEET A-4, BUT THERE WERE NOT
 ANY CORRECTIONS. PLEASE BE ADVISED THAT THIS COMMENT
 HAS NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE
 THIRD REVIEW, IF IT IS NECESSARY TO REJECT THE
 SUBMITTED PLAN A THIRD TIME FOR THE SAME REASONS, AN
 ADDITIONAL PLAN REVIEW IS REQUIRED. FLORIDA STATUTES
 STATE: ?WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW. FS 553.80(2)(B)?
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. INCLUDE THE 20 AMP BRANCH CIRCUIT REQUIRED
 FOR BATHROOM RECEPTACLE OUTLETS. NEC 210.8, 210.11,
 210.12, 215.5, 408.4; FBC RE3 706.2, RE 3902, RE 3703
 3. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE4003.11
 4. LIGHT IN CLOSET IS SHOWN AS A RECESS LIGHT. PER
 CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS
 AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. NEC
 410.16; FBC RE4003.12
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 6. PROVIDE COMPLIANCE FOR ANY NEW OR ALTERED CIRCUIT:
 "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION". NEC 210.12; FBC RE3902.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  