| 2017-10-27 09:31:17 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| | 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC |
| | 107.2.1 |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. INCLUDE THE 20 AMP BRANCH CIRCUIT REQUIRED |
| | FOR BATHROOM RECEPTACLE OUTLETS. NEC 210.8, 210.11, |
| | 210.12, 215.5, 408.4; FBC RE3 706.2, RE 3902, RE 3703 |
| | 3. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| | SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC |
| | 410.10(D); FBC RE4003.11 |
| | 4. LIGHT IN CLOSET IS SHOWN AS A RECESS LIGHT. PER |
| | CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS |
| | AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| | PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. NEC |
| | 410.16; FBC RE4003.12 |
| | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 6. PROVIDE COMPLIANCE FOR ANY NEW OR ALTERED CIRCUIT: |
| | "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| | PROTECTION". NEC 210.12; FBC RE3902.12 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |