| Plan Review Notes For Permit 17100041 |
| Permit Number |
17100041 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-05 16:18:39 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 | | | 2. PROVIDE RISER DIAGRAM. NEC 215.5; FBC 107.2.1 | | | 3. PROVIDE LOAD CALCULATION FOR PANEL, INCLUDING ALL | | | LOADS TO CONFIRM PANEL SIZE IS ADEQUATE FOR ADDITIONAL | | | LOAD. NEC 220 | | | 4. SHOW ALL CIRCUITS REQUIRED ON PLAN. I DO NOT SEE ANY | | | CIRCUITS INDICATED FOR TANKLESS WATER HEATER OR | | | DISPOSAL. FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|