| Plan Review Notes For Permit 17090775 |
| Permit Number |
17090775 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-13 13:48:33 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | PROVIDE PLUMBING RISER DIAGRAM AS STATED ON CONTRACT | | | AND PER WPB AMEND TO FBC 107.3.5.3(11) | | | | | | PROVIDE FLOOR PLAN SHOWING WHOLE HOUSE AS STATED ON | | | CONTRACT AND PER WPB AMEND TO FBC 107.2.1 | | | | | | SUBMIT SPECS FOR SHOWER CONTROLS VALES FBC P2708.3 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] | | | 561-805-6720 | | | |
|