| 2017-10-18 15:36:13 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO SETS OF CONSTRUCTION DOCUMENTS THAT SHOW |
| | THE EXISTING FLOOR PLAN AND THE PROPOSED FLOOR PLAN. |
| | PROVIDE STRUCTURAL DETAILS OF THE NEW ROOF OPENING FOR |
| | THE SKYLIGHT. FBC 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED |
| | AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | 2) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE NEW |
| | SKYLIGHT. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT |
| | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR THE SKYLIGHTS. |
| | |
| | 3) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS AND |
| | COMPONENT AND CLADDING DESIGN PRESSURES PURSUANT TO |
| | FBC-R301.2. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC - R314.3.1 WHEN |
| | ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A PERMIT |
| | OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR |
| | CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING |
| | UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS |
| | REQUIRED FOR NEW DWELLINGS. |
| | |
| | |
| | |
| | |
| | |