Date Text
2017-11-13 09:57:23PLAN DENIED
 1) PLEASE MARK ON PLAN WITCH A/C UNIT
 IS # 1 AND 2 PER SECTION 107 FBC
 2) REFER TO SECTION M 1602.4 BALANCED RETURN AIR
 FOR MASTER BEDROOM 1ST. FLOOR 2014 RESIDENTIAL CODE
 3) REFER TO SECTION M 1507.4 EXHAUST RATES. NEED
 EXHAUST FAN IN MASTER BATH NOT IN TOLIT ROOM. 2014
 RESIDENTIAL CODE.
 4) PROVIDE COMPLETE ADDRESS ON PLANS.
  