| 2017-12-12 16:53:01 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS |
| | SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. |
| | R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 2- SPECIFY THE SIZE OF THE TRANSFER DUCT FOR THE |
| | BALANCED RETURN AIR FOR ALL THE ROOMS ON THE FIRST |
| | FLOOR AND ALL THE ROOMS ON THE SECOND FLOOR SHOWING |
| | COMPLIANCE WITH SEC. M1602.4 FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | NOTE: WHEN SIZING THE DUCT KEEP IN MIND THAT NEED TO |
| | TAKE INTO CONSIDERATION ALL THE SUPPLY AIR THAT IS |
| | GOING INTO THE MASTER BEDROOM. SEE EXCEPTION #3 OF SEC. |
| | M1602.4. |
| | |
| | RESPONSE: SIZE OF TRANSFER DUCT SPECIFIED FOR THE |
| | MASTER BEDROOM DOESN'T COMPLY. REVISE AS REQUIRED. |
| | NOTE: KEEP IN MIND THAT NEED TO CONSIDER ALL THE SUPPLY |
| | TO THE MASTER BEDROOM, INCLUDING CLOSETS, BATHROOMS, |
| | ETC. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |