| 2017-10-20 10:53:16 | |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS REQUIRED |
| | WITHIN 3 FEET OF EACH BASIN. PROVIDE CORRECTION. |
| | NEC 210.11(C)(3), 210.52(D); FBC RE 3703.4, 3901.6 |
| | PAGE E-101 GUEST STUDY BATHROOM, PAGE E-102 BEDROOM #2 |
| | BATHROOM |
| | |
| | PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE. NEC |
| | 210.8; FBC RE3902.2 |
| | INCLUDES GARAGE DOOR OPENER. |
| | |
| | SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN |
| | 6 FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. |
| | NEC 210.52; FBC RE3901.2.1 |
| | PAGE E-101 GREAT ROOM, PAGE E-102 MASTER SUTIE, BEDROOM |
| | #2 |
| | |
| | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| | CODE. SHOW ON PLAN ALL EXISTING ALARMS. |
| | IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS NEW |
| | INSTALLATIONS. FBC R314.3, FBC 107.2 |
| | PAGE E-102 TOP OF STAIRS AND MEDIA LOFT WHICH IS WITHIN |
| | 10' OF SLEEPING AREAS. |
| | |
| | SHOW LOCATION OF SERVICE AND PANELS, NO LOCATION SHOWN. |
| | FBC RE3601.6.2 SERVICE DISCONNECT LOCATION. |
| | PAGE E-101 |
| | |
| | CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR |
| | CORD-SUSPENDED-LUMINAIRES, LIGHTING TRACK, PENDANTS, |
| | AND CEILING-SUSPENDED (PADDLE) FANS SHALL NOT HAVE ANY |
| | PARTS LOCATED WITHIN A ZONE MEASURED 3 FEET |
| | (914 MM) HORIZONTALLY AND 8 FEET (2438 MM) VERTICALLY |
| | FROM THE TOP OF A BATHTUB RIM FBC RE4003.11 |
| | LIGHT OVER TUB ON PAGE E-102 |
| | |
| | ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY |
| | IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED |
| | FROM ALL OTHERS. SPARE POSITIONS THAT CONTAIN UNUSED |
| | OVERCURRENT DEVICES OR SWITCHES SHALL BE DESCRIBED |
| | ACCORDINGLY. THE IDENTIFICATION SHALL BE INCLUDED IN A |
| | CIRCUIT DIRECTORY LOCATED ON THE FACE OF THE |
| | PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR. CIRCUITS |
| | SHALL NOT BE DESCRIBED IN A MANNER THAT DEPENDS |
| | ON TRANSIENT CONDITIONS OF OCCUPANCY. FBC RE3706.2 |
| | PANEL SCHEDULES NOT DESCRIPTIVE ENOUGH FOR CIRCUITS. |