Plan Review Notes
Plan Review Notes For Permit 17090751
Permit Number 17090751
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-01 16:53:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR
 THE HEATING AND COOLING EQUIPMENT AS REQUIRED BY FBC-R
 - M1401.3 SIZING. HEATING AND COOLING EQUIPMENT SHALL
 BE SIZED BASED ON BUILDING LOADS CALCULATED IN
 ACCORDANCE WITH ACCA MANUAL J OR OTHER APPROVED HEATING
 AND COOLING CALCULATION METHODOLOGIES.
  
 2) THE TRANSFER DUCT FOR THE FIRST FLOOR MASTER SUITE
 IS UNDER SIZED. ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED IN SIZING THE TRANSFER DUCTS PER
 FBC-R - M 1602.4.
  
 3) SUBMIT TWO SETS OF THE SPECIFICATIONS FOR THE
 OUTDOOR GAS COOKTOP AND THE EXHAUST HOOD THAT ARE
 LOCATED ON THE COVERED PORCH. FBC 107.2.1
  
  
  
  
  