| Plan Review Notes For Permit 17090751 |
| Permit Number |
17090751 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-01 16:53:29 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR | | | THE HEATING AND COOLING EQUIPMENT AS REQUIRED BY FBC-R | | | - M1401.3 SIZING. HEATING AND COOLING EQUIPMENT SHALL | | | BE SIZED BASED ON BUILDING LOADS CALCULATED IN | | | ACCORDANCE WITH ACCA MANUAL J OR OTHER APPROVED HEATING | | | AND COOLING CALCULATION METHODOLOGIES. | | | | | | 2) THE TRANSFER DUCT FOR THE FIRST FLOOR MASTER SUITE | | | IS UNDER SIZED. ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED IN SIZING THE TRANSFER DUCTS PER | | | FBC-R - M 1602.4. | | | | | | 3) SUBMIT TWO SETS OF THE SPECIFICATIONS FOR THE | | | OUTDOOR GAS COOKTOP AND THE EXHAUST HOOD THAT ARE | | | LOCATED ON THE COVERED PORCH. FBC 107.2.1 | | | | | | | | | | | | | | | |
|