2017-10-26 13:55:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SERVICE CONDUCTORS FROM METER CAN TO MCB PANELS IS
 SHOWN AS # 1 WIRE TO A 150 AMP MAIN BREAKER. WIRE SIZES
 FROM NEC 310.15(B)(7), OR FBC RE TABLE E3603.1, CAN
 ONLY BE USED WHEN THE SERVICE CONDUCTOR SUPPLIES 100%
 OF THE LOAD. SINCE THIS IS NOT THE CASE, PROVIDE
 CORRECTED WIRE SIZE FROM METER CAN TO PANELS. NEC
 310.15(B)(7) AND (B)(15); FBC RE TABLE E3601.3
 2. SERVICE CONDUCTORS FROM THE METER CAN TO THE MCB
 PANELS SHOULD NOT INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE 3607
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 4. CLARIFICATION REQUIRED FOR THE GROUNDING ELECTRODE
 CONDUCTOR (GEC) SIZE. IF THE GEC IS ATTACHED TO THE CWP
 AS SHOWN, THEN IT IS TOO SMALL, ASSUMING THE SIZE OF
 SERVICE CONDUCTOR FROM FPL IS RATED FOR 300 AMPS. IF
 THERE IS NOT 10 FEET OF BURIED METAL CWP, THEN THE
 CURRENT SIZE IS ADEQUATE TO THE FOOTER STEEL AND GROUND
 RODS. IN THIS CASE, REMOVE THE CWP REFERENCE ON THE
 RISER DIAGRAM GROUNDING. NEC 250.52; FBC RE 3608.1
 5. SHOW LOCATION OF SERVICE AND ELECTRICAL PANELS ON
 PLAN. HOW FAR FROM THE METER CAN IS THE LOCATION OF THE
 PANELS? SERVICE ENTRANCE CONDUCTORS WITHOUT AN
 OVERCURRENT PROTECTION SHALL NOT BE PERMITTED TO BE RUN
 INSIDE THE BUILDING MORE THAN 8 FEET. EACH OF THE MAIN
 CIRCUIT BREAKERS ARE REQUIRED TO BE IN SAME LOCATION
 (GROUPED). FBC 107.2.1; NEC 230.72
 6. FOR POOL PANEL, DEMAND FACTORS CANNOT BE USED. THE
 DEMAND FACTORS ARE ONLY FOR FEEDERS RATED 100 AMPS OR
 GREATER. SIZE WIRING AND OVERCURRENT PROTECTION FOR THE
 LOAD OF THE PANEL. PROVIDE CORRECTION. NEC 220.82; FBC
 RE 3702.1
 7. BREAKER FOR POOL PUMP IS REQUIRED TO BE GFCI
 PROTECTED. NEC 680.21(C); FBC RE 4203.1.3
 8. PANEL A, CIRCUIT 1,3 SHOWS A # 6 ROMEX WIRE ON A 60
 AMP BREAKER. #6 ROMEX WIRE IS NOT RATED FOR 60 AMPS.
 PROVIDE CORRECTION. NEC 334.80; FBC RE3705.4.4
 9. WATER HEATER IS SHOWN ON ELECTRICAL PLAN, BUT THERE
 IS NO LOAD INCLUDED FOR LOAD CALCULATION OR CIRCUIT
 SHOWN FOR WATER HEATER. THERE IS ALSO NO PLUMBING PLAN
 PROVIDED TO VERIFY THE TYPE OF WATER HEATER. PROVIDE
 CORRECTION. NEC 220; FBC 107.2.1
 10. NOTE 21 OF ELECTRICAL NOTES STATES THAT RECEPTACLES
 SHALL BE TAMPER RESISTANT PER NEC 2008, 406.11. THIS IS
 NOT THE CURRENT CODE OR CORRECT CODE SECTION. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 11. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE,
 INCLUDING GARAGE DOOR OPENER.. NEC 210.8; FBC RE3902.2
 12. MASTER AND GUEST BATH SHOW A CHANDELIER OVER THE
 TUB. NO PARTS OF CORD-CONNECTED LUMINAIRES, CHAIN-,
 CABLE-, OR CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK,
 PENDANTS, OR CEILING-SUSPENDED (PADDLE) FANS SHALL BE
 LOCATED WITHIN A ZONE MEASURED 3 FEET HORIZONTALLY AND
 8 FEET VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR
 SHOWER STALL THRESHOLD. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE 4003.11
 13. ALL WALK IN CLOSETS SHOW STANDARD RECESS LIGHTS
 WITH LED. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. NEC 410.16; FBC RE4003.12
 14. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR LOW VOLTAGE SYSTEMS AND POOL. FBC 105.1,
 107.2.1
 15. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 16. SECOND FLOOR PLAN, AT TOP OF STAIRS AND IN HALLWAY,
 A REGULAR SMOKE ALARM IS SHOWN. PROVIDE CARBON MONOXIDE
 ALARMS WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING
 PURPOSES. FBC R315.1
 17. SMOKE ALARMS IN SEVERAL LOCATION ARE SHOWN WITHIN 3
 FEET OF A CEILING FAN. PER THE FIRE CODE, SMOKE ALARMS
 SHALL BE AT LEAST 3 FEET FROM CEILING FANS OR
 MECHANICAL GRILLS. PROVIDE CORRECTION. NFPA 72;
 29.8.3.4, AND 6, AND 7
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  