2017-11-01 11:05:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A-301 UNDER ENGINEERING CRITERIA THE
 EXPOSURE CATEGORY IS LISTED AS "D". ON SHEETS S-2 AND
 S-3 THE EXPOSURE CATEGORY IS SPECIFIED AS "C" IN THE
 CAST-CRETE UPLIFT CALCULATIONS AND THE ROOF FRAMING
 NOTES. PLEASE CHANGE AS NECESSARY SO THAT ONLY ONE
 EXPOSURE CATEGORY IS SPECIFIED. BASED ON
 FBC-R301.2.1.4, THIS STRUCTURE IS LOCATED IN EXPOSURE
 "C". THE COMPONENT AND CLADDING PRESSURES LISTED ON
 SHEET A-301 SHOULD BE REDUCED FOR EXPOSURE "C".
  
 2) SHOW COMPLIANCE WITH FBC-R807.1 ATTIC ACCESS.
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION
 SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT
 EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL
 HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL
 HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING
 FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING
 MEMBERS. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS
 THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND
 SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE AH 160 ROOF TILE
 ADHESIVE AND THE SLIDING GLASS DOOR.
  
 4) THE PRODUCT APPROVAL FOR THE SANTAFE CLAY ROOF TILE,
 NOA NO.12-0210.01, EXPIRED ON 2/01/2016. SUBMIT TWO
 CURRENT PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD. FBC 107.3.4
  
 5)THE DESIGN PRESSURES (+36.0 PSF, -42.0 PSF) ON THE
 PRODUCT APPROVAL FOR THE 16' WIDE CLOPAY SECTIONAL
 GARAGE DOOR FL16107 DO NOT MEET THE REQUIRED GARAGE
 DOOR PRESSURES (+42.25 PSF, -59.22 PSF) THAT ARE
 SPECIFIED ON SHEET A-301. FBC-R 301.2.1
  
 6) THE PRODUCT APPROVALS SUBMITTED FOR THE ETO WOOD
 OUTSWING DOORS DO NOT HAVE A COVERSHEET WITH A FL
 NUMBER OR AN NOA NO. TO IDENTIFY IT. THE EDITIONS OF
 THE FBC LISTED ON THE DRAWINGS ARE THE 2007 AND 2010
 EDITIONS. THE PRODUCT APPROVALS ARE REQUIRED TO
 REFERENCE THE 2014 EDITION OF THE FBC. THE DESIGN
 PRESSURES (+60 PSF, -60PSF) ON THE DOCUMENTS THAT WERE
 SUBMITTED DO NOT MEET THE REQUIRED DOOR PRESSURES
 (+48.15 PSF, -59.22 PSF) THAT ARE SPECIFIED ON SHEET
 A-301. FBC-R 301.2.1
  
 7) INDICATE THE SPECIFIC DOORS THAT EACH OF THE DOOR
 PRODUCT APPROVALS ARE INTENDED FOR. YOU CAN USE THE
 DOOR NUMBERING FROM THE PLANS. FBC 107.2.1
  
 8) SPECIFY THE SIZE OF THE DOOR SIDE LIGHTS ON THE
 PLANS. ON THE PRODUCT APPROVAL FOR THE DOOR WITH SIDE
 LIGHTS, MARK THE APPROPRIATE SIZE DOOR, SIDE LIGHTS AND
 DESIGN PRESSURES FROM THE ONES THAT ARE LISTED IN THE
 TABLES. FBC-R301.2.1 & FBC 107.2.1
  
 9) MARK THE APPROPRIATE SIZE AND DESIGN PRESSURES ON
 THE PRODUCT APPROVAL ( NOA NO.16-0629.22 ) FOR THE
 FIXED CASEMENT WINDOW. IDENTIFY WHICH WINDOW THIS
 PRODUCT APPROVAL APPLIES TO. FBC 107.2.1
  
 10) SUBMIT SIGNED AND SEALED RAS117 CALCULATIONS FOR
 ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7
 FOR THE TARCO MODIFIED BITUMEN ROOFING MATERIAL (NOA
 NO. 12-0703.06).
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  