| 2017-11-01 11:05:33 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ON SHEET A-301 UNDER ENGINEERING CRITERIA THE |
| | EXPOSURE CATEGORY IS LISTED AS "D". ON SHEETS S-2 AND |
| | S-3 THE EXPOSURE CATEGORY IS SPECIFIED AS "C" IN THE |
| | CAST-CRETE UPLIFT CALCULATIONS AND THE ROOF FRAMING |
| | NOTES. PLEASE CHANGE AS NECESSARY SO THAT ONLY ONE |
| | EXPOSURE CATEGORY IS SPECIFIED. BASED ON |
| | FBC-R301.2.1.4, THIS STRUCTURE IS LOCATED IN EXPOSURE |
| | "C". THE COMPONENT AND CLADDING PRESSURES LISTED ON |
| | SHEET A-301 SHOULD BE REDUCED FOR EXPOSURE "C". |
| | |
| | 2) SHOW COMPLIANCE WITH FBC-R807.1 ATTIC ACCESS. |
| | BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION |
| | SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT |
| | EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL |
| | HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL |
| | HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING |
| | FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING |
| | MEMBERS. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS |
| | THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND |
| | SHALL BE LOCATED IN A HALLWAY OR OTHER READILY |
| | ACCESSIBLE LOCATION. |
| | |
| | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR THE AH 160 ROOF TILE |
| | ADHESIVE AND THE SLIDING GLASS DOOR. |
| | |
| | 4) THE PRODUCT APPROVAL FOR THE SANTAFE CLAY ROOF TILE, |
| | NOA NO.12-0210.01, EXPIRED ON 2/01/2016. SUBMIT TWO |
| | CURRENT PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD. FBC 107.3.4 |
| | |
| | 5)THE DESIGN PRESSURES (+36.0 PSF, -42.0 PSF) ON THE |
| | PRODUCT APPROVAL FOR THE 16' WIDE CLOPAY SECTIONAL |
| | GARAGE DOOR FL16107 DO NOT MEET THE REQUIRED GARAGE |
| | DOOR PRESSURES (+42.25 PSF, -59.22 PSF) THAT ARE |
| | SPECIFIED ON SHEET A-301. FBC-R 301.2.1 |
| | |
| | 6) THE PRODUCT APPROVALS SUBMITTED FOR THE ETO WOOD |
| | OUTSWING DOORS DO NOT HAVE A COVERSHEET WITH A FL |
| | NUMBER OR AN NOA NO. TO IDENTIFY IT. THE EDITIONS OF |
| | THE FBC LISTED ON THE DRAWINGS ARE THE 2007 AND 2010 |
| | EDITIONS. THE PRODUCT APPROVALS ARE REQUIRED TO |
| | REFERENCE THE 2014 EDITION OF THE FBC. THE DESIGN |
| | PRESSURES (+60 PSF, -60PSF) ON THE DOCUMENTS THAT WERE |
| | SUBMITTED DO NOT MEET THE REQUIRED DOOR PRESSURES |
| | (+48.15 PSF, -59.22 PSF) THAT ARE SPECIFIED ON SHEET |
| | A-301. FBC-R 301.2.1 |
| | |
| | 7) INDICATE THE SPECIFIC DOORS THAT EACH OF THE DOOR |
| | PRODUCT APPROVALS ARE INTENDED FOR. YOU CAN USE THE |
| | DOOR NUMBERING FROM THE PLANS. FBC 107.2.1 |
| | |
| | 8) SPECIFY THE SIZE OF THE DOOR SIDE LIGHTS ON THE |
| | PLANS. ON THE PRODUCT APPROVAL FOR THE DOOR WITH SIDE |
| | LIGHTS, MARK THE APPROPRIATE SIZE DOOR, SIDE LIGHTS AND |
| | DESIGN PRESSURES FROM THE ONES THAT ARE LISTED IN THE |
| | TABLES. FBC-R301.2.1 & FBC 107.2.1 |
| | |
| | 9) MARK THE APPROPRIATE SIZE AND DESIGN PRESSURES ON |
| | THE PRODUCT APPROVAL ( NOA NO.16-0629.22 ) FOR THE |
| | FIXED CASEMENT WINDOW. IDENTIFY WHICH WINDOW THIS |
| | PRODUCT APPROVAL APPLIES TO. FBC 107.2.1 |
| | |
| | 10) SUBMIT SIGNED AND SEALED RAS117 CALCULATIONS FOR |
| | ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7 |
| | FOR THE TARCO MODIFIED BITUMEN ROOFING MATERIAL (NOA |
| | NO. 12-0703.06). |
| | |
| | 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |