| Date |
Text |
| 2017-10-01 15:07:04 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17090731 |
| | ADD: 1200 S. FLAGLER DR. SUITE: 1903 |
| | CONT: ALL CITY TILE INSTALLATION, INC. |
| | TEL: 561-252-5553 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUNDAY, OCT. 01/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2) THE USE OF ? INCH SOUND CONTROL TO BE USED AS |
| | UNDERLAYMENT FOR CARPETING WILL NEED TO SHOW THE |
| | UNDERLAYMENT AND CARPET COMBINED WERE TESTED TO THE |
| | 2014 FBC-B SECTIONS: |
| | |
| | 2A) 804.4.1 TEST REQUIREMENT. IN ALL OCCUPANCIES, |
| | INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR |
| | PART 1630) OR WITH ASTM D 2859. |
| | |
| | 2B) 804.4.2 MINIMUM CRITICAL RADIANT FLUX. IN ALL |
| | OCCUPANCIES, INTERIOR FLOOR FINISH AND FLOOR COVERING |
| | MATERIALS IN ENCLOSURES FOR STAIRWAYS AND RAMPS, EXIT |
| | PASSAGEWAYS, CORRIDORS AND ROOMS OR SPACES NOT |
| | SEPARATED FROM CORRIDORS BY PARTITIONS EXTENDING FROM |
| | THE FLOOR TO THE UNDERSIDE OF THE CEILING SHALL |
| | WITHSTAND A MINIMUM CRITICAL RADIANT FLUX. THE MINIMUM |
| | CRITICAL RADIANT FLUX SHALL NOT BE LESS THAN CLASS I IN |
| | GROUPS I-1, I-2 AND I-3 AND NOT LESS THAN CLASS II IN |
| | GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S. |
| | EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE |
| | PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE |
| | REQUIRED, AND MATERIALS COMPLYING WITH DOC FF-1 ?PILL |
| | TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D 2859 ARE |
| | PERMITTED IN ANY AREA WHERE CLASS II MATERIALS ARE |
| | REQUIRED. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |