Plan Review Notes
Plan Review Notes For Permit 17090731
Permit Number 17090731
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-01 15:07:042014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17090731
 ADD: 1200 S. FLAGLER DR. SUITE: 1903
 CONT: ALL CITY TILE INSTALLATION, INC.
 TEL: 561-252-5553
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY, OCT. 01/ 2017
 ACTION: DENIED
  
 1) BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) THE USE OF ? INCH SOUND CONTROL TO BE USED AS
 UNDERLAYMENT FOR CARPETING WILL NEED TO SHOW THE
 UNDERLAYMENT AND CARPET COMBINED WERE TESTED TO THE
 2014 FBC-B SECTIONS:
  
 2A) 804.4.1 TEST REQUIREMENT. IN ALL OCCUPANCIES,
 INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY WITH THE
 REQUIREMENTS OF THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR
 PART 1630) OR WITH ASTM D 2859.
  
 2B) 804.4.2 MINIMUM CRITICAL RADIANT FLUX. IN ALL
 OCCUPANCIES, INTERIOR FLOOR FINISH AND FLOOR COVERING
 MATERIALS IN ENCLOSURES FOR STAIRWAYS AND RAMPS, EXIT
 PASSAGEWAYS, CORRIDORS AND ROOMS OR SPACES NOT
 SEPARATED FROM CORRIDORS BY PARTITIONS EXTENDING FROM
 THE FLOOR TO THE UNDERSIDE OF THE CEILING SHALL
 WITHSTAND A MINIMUM CRITICAL RADIANT FLUX. THE MINIMUM
 CRITICAL RADIANT FLUX SHALL NOT BE LESS THAN CLASS I IN
 GROUPS I-1, I-2 AND I-3 AND NOT LESS THAN CLASS II IN
 GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S.
 EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE
 PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE
 REQUIRED, AND MATERIALS COMPLYING WITH DOC FF-1 ?PILL
 TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D 2859 ARE
 PERMITTED IN ANY AREA WHERE CLASS II MATERIALS ARE
 REQUIRED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  