| Plan Review Notes For Permit 17090683 |
| Permit Number |
17090683 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-28 17:47:08 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- RAS 117 CALCULATIONS SUBMITTED: | | | A) THE ADDRESS SHOWN IS INCORRECT. THIS BUILDING IS | | | LOCATED IN WEST PALM BEACH NOT RIVIERA BEACH. THESE ARE | | | TWO DIFFERENT MUNICIPALITIES. REVISE AS REQUIRED. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | B) THIS BUILDING IS LOCATED IN EXPOSURE "C" NOT | | | EXPOSURE "B". REVISE AS REQUIRED . SEC. R301.2.1.4 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | C) ACCORDING TO FIGURE R301.2(7) OF FBC-RESIDENTIAL THE | | | MINIMUM DIMENSION FOR ROOF ZONES 2 AND 3 IS 4'-0" NOT | | | 3'-0". REVISE THE ROOF ZONES DIMENSIONS AS REQUIRED. | | | | | | D) CLARIFY WHAT'S ASCE 7-0.10 SPECIFIED ON THE MIDDLE | | | OF THE SHEET SUBMITTED. DO YOU MEAN ASCE 7-10?. REVISE | | | AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|