| Plan Review Notes For Permit 17090634 |
| Permit Number |
17090634 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-19 16:46:41 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE EQUIPMENT INFORMATION ON FORM R405-2014 DOES NOT | | | MATCH THE EQUIPMENT SIZING CALCULATIONS OR THE | | | MECHANICAL PLANS. FBC-R103.2 | | | | | | 2) THE RETURN AIR TRANSFER DUCT FOR THE MASTER BEDROOM | | | SUITE IS UNDERSIZED. ALL SUPPLY AIR INTO THE MASTER | | | SUITE SHALL BE INCLUDED WHEN CALCULATING THE TRANSFER | | | DUCT SIZING. FBCR-M1602.4 | | | | | | |
|