2017-10-19 16:46:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE EQUIPMENT INFORMATION ON FORM R405-2014 DOES NOT
 MATCH THE EQUIPMENT SIZING CALCULATIONS OR THE
 MECHANICAL PLANS. FBC-R103.2
  
 2) THE RETURN AIR TRANSFER DUCT FOR THE MASTER BEDROOM
 SUITE IS UNDERSIZED. ALL SUPPLY AIR INTO THE MASTER
 SUITE SHALL BE INCLUDED WHEN CALCULATING THE TRANSFER
 DUCT SIZING. FBCR-M1602.4
  
  