2017-10-02 11:01:33THIS PLAN HAS BEEN PASSED PROVISIONALLY:
  
 FOR FINAL INSPECTION:
 1. PROVIDE ACCURATE LOAD CALCULATION AND PANEL
 SCHEDULE. LOAD CALCULATION ONLY SHOWS 1 SMALL APPLIANCE
 CIRCUIT IN KITCHEN, MINIMUM OF 2 IS REQUIRED. NEC
 210.52 (B1) NEC 220.52 (A).
 GENERAL LIGHTING IS NOT A SUFFICIENT DESCRIPTION FOR
 CIRCUITS ON THE PANEL SCHEDULE.
  
 FOR ROUGH INSPECTION:
 1. MINIMUM OF 2 SMALL APPLIANCE CIRCUITS FOR KITCHEN.
 NEC 210.52 (B1) NEC 220.52 (A)
  
 2.WP/GFCI RECEPTACLE REQUIRED ON FRONT OF DWELLING NEC
 210.52(E1)
  
 3. NEED RECEPTACLE IN FOYER NEC 210.52(A2)
  
 4. NEED GFCI RECEPTACLE WITH 3 FEET OF SINK IN BATHROOM
 ATTACHED TO BEDROOM #1.
  
 5. ATTIC ACCESS NEEDS A LIGHT AND SWITCH NEC 210.70
 (A3)
  
 6. SMOKE ALARM OUTSIDE OF BEDROOMS #1&2 MUST BE A
 SA/CMD. FBC R315
  
 PLAN HAS BEEN MARKED ACCORDINGLY WITH CORRECTIONS.
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE