Plan Review Notes
Plan Review Notes For Permit 17090634
Permit Number 17090634
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-19 15:27:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC
 107.2.1
  
 2) PROVIDE A DRAINAGE PLAN THAT SHOWS COMPLIANCE WITH
 FBC - R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 3) ON SHEET S.1, UNDER DESIGN CRITERIA LETTER (D) THE
 LAST ZONE SHOULD BE NUMBER 5, NOT 3. FBC-R FIGURE
 301.2(7)
  
 4) THE DOOR BETWEEN THE GARAGE AND THE RESIDENCE SHALL
 COMPLY WITH FBC-R 302.5.1 AND BE EQUIPPED WITH A
 SELF-CLOSING DEVICE.
  
 5) THE DESIGN PARAMETERS ON SHEET S.3 SPECIFY EXPOSURE
 CATEGORY "D". ON SHEET S.3, EXPOSURE "C" IS SPECIFIED
 AND THE DESIGN PRESSURES THAT ARE PROVIDED ARE FOR
 EXPOSURE "C". THE STRUCTURE IS LOCATED IN EXPOSURE "C".
 PLEASE CORRECT THE EXPOSURE ON SHEET S.3.
 FBC-R301.2.1.4
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE DRY
 STACK STONE CLADDING. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 OUTSWING FRONT DOOR WITH ONE SIDELIGHT. THE ONE
 SUBMITTED (JELD-WEN, FL 11136-R5) IS FOR A SINGLE DOOR
 WITH NO SIDELIGHTS. PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD.
  
 8) FBC ENERGY CONSERVATION SECTION R103.1.1 REQUIRES
 THE OWNER/AGENT TO SIGN AND DATE ENERGY FORM R405-2014.
  
 9) THE ENERGY FORM R405-2014, CONTAINS SOME ERRORS. THE
 SQUARE FOOTAGE OF CONDITIONED SPACE SHOULD BE 2163. THE
 NUMBER OF BEDROOMS IS 4. THE ADDRESS OF THE PROJECT IS
 SHELLY ROAD, WEST PALM BEACH FL.
  
 10) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  