| 2017-10-19 15:27:55 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC |
| | 107.2.1 |
| | |
| | 2) PROVIDE A DRAINAGE PLAN THAT SHOWS COMPLIANCE WITH |
| | FBC - R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE |
| | DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED |
| | POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS |
| | SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| | INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | 3) ON SHEET S.1, UNDER DESIGN CRITERIA LETTER (D) THE |
| | LAST ZONE SHOULD BE NUMBER 5, NOT 3. FBC-R FIGURE |
| | 301.2(7) |
| | |
| | 4) THE DOOR BETWEEN THE GARAGE AND THE RESIDENCE SHALL |
| | COMPLY WITH FBC-R 302.5.1 AND BE EQUIPPED WITH A |
| | SELF-CLOSING DEVICE. |
| | |
| | 5) THE DESIGN PARAMETERS ON SHEET S.3 SPECIFY EXPOSURE |
| | CATEGORY "D". ON SHEET S.3, EXPOSURE "C" IS SPECIFIED |
| | AND THE DESIGN PRESSURES THAT ARE PROVIDED ARE FOR |
| | EXPOSURE "C". THE STRUCTURE IS LOCATED IN EXPOSURE "C". |
| | PLEASE CORRECT THE EXPOSURE ON SHEET S.3. |
| | FBC-R301.2.1.4 |
| | |
| | 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE DRY |
| | STACK STONE CLADDING. FBC 107.3.4 - PROVIDE TWO SETS OF |
| | PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | OUTSWING FRONT DOOR WITH ONE SIDELIGHT. THE ONE |
| | SUBMITTED (JELD-WEN, FL 11136-R5) IS FOR A SINGLE DOOR |
| | WITH NO SIDELIGHTS. PROVIDE TWO SETS OF PRODUCT |
| | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. |
| | |
| | 8) FBC ENERGY CONSERVATION SECTION R103.1.1 REQUIRES |
| | THE OWNER/AGENT TO SIGN AND DATE ENERGY FORM R405-2014. |
| | |
| | 9) THE ENERGY FORM R405-2014, CONTAINS SOME ERRORS. THE |
| | SQUARE FOOTAGE OF CONDITIONED SPACE SHOULD BE 2163. THE |
| | NUMBER OF BEDROOMS IS 4. THE ADDRESS OF THE PROJECT IS |
| | SHELLY ROAD, WEST PALM BEACH FL. |
| | |
| | 10) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |