Plan Review Notes
Plan Review Notes For Permit 17090494
Permit Number 17090494
Review Stop M
Sequence Number 1
Notes
Date Text
2017-09-29 10:42:161ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL, ENERGY
 CONSERVATION
 PERMIT #17090494
 9/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) UNDER THE PROPOSED EQUIPMENT SCHEDULE PLEASE ADD THE
 COOLING AND HEATING CAPACITIES OF THE SYSTEM, AND
 SUBMIT AN AHRI CERTIFICATE- SECTION R101.4.7 FBC-14
 MECHANICAL.
  
 2) SHOW THE AIRFLOW IN CFMS AT EACH DIFFUSER AND RETURN
 GRILL- SECTION M1602.4 FBC-14 RESIDENTIAL.
  
 3) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD AND TIE DOWN OF THE UNIT- SECTIONS
 M1305.1.4.1 & M1401.4.
  
 4) THE ENGINEER'S LETTER AND THE ENERGY CALCULATIONS
 ARE INDICATING THE NEW WINDOWS HAVE U-FACTORS OF 0.34
 AND SHGC OF 0.23, HOWEVER THE ORIGINAL PLANS UNDER
 PERMIT #16100865 DO NOT INDICATE THESE VALUES. PLEASE
 PROVIDE DOCUMENTATION FROM THE MANUFACTURER TO VERIFY
 COMPLIANCE.
  