| 2017-09-29 10:42:16 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL, ENERGY | | | CONSERVATION | | | PERMIT #17090494 | | | 9/29/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) UNDER THE PROPOSED EQUIPMENT SCHEDULE PLEASE ADD THE | | | COOLING AND HEATING CAPACITIES OF THE SYSTEM, AND | | | SUBMIT AN AHRI CERTIFICATE- SECTION R101.4.7 FBC-14 | | | MECHANICAL. | | | | | | 2) SHOW THE AIRFLOW IN CFMS AT EACH DIFFUSER AND RETURN | | | GRILL- SECTION M1602.4 FBC-14 RESIDENTIAL. | | | | | | 3) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | | CONDENSER PAD AND TIE DOWN OF THE UNIT- SECTIONS | | | M1305.1.4.1 & M1401.4. | | | | | | 4) THE ENGINEER'S LETTER AND THE ENERGY CALCULATIONS | | | ARE INDICATING THE NEW WINDOWS HAVE U-FACTORS OF 0.34 | | | AND SHGC OF 0.23, HOWEVER THE ORIGINAL PLANS UNDER | | | PERMIT #16100865 DO NOT INDICATE THESE VALUES. PLEASE | | | PROVIDE DOCUMENTATION FROM THE MANUFACTURER TO VERIFY | | | COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|