| | RECEIVED REVISED CALCULATIONS FROM NICOLE BLACKWELL |
| | FROM QUICKCALCS. |
| | (ENERGY CALCULATIONS AND EQUIPMENT SIZING |
| | CALCULATIONS). JG. |
| | |
| | |
| | |
| | EQUIPMENT SIZING CALCULATIONS REVISION COURTESY REVIEW: |
| | 1- THE NUMBER OF PEOPLE SHOWN ON THE EQUIPMENT SIZING |
| | CALCULATIONS DOESN'T MATCH THE NUMBER OF PEOPLE SHOWN |
| | ON THE ENERGY CALCULATIONS. REVISE AS REQUIRED. |
| | |
| | NEW COMMENT: |
| | 1- NUMBER OF PEOPLE SHOWN ON THE ENERGY CALCULATIONS |
| | WAS CHANGED FROM 8 PEOPLE TO 12 PEOPLE. 8 PEOPLE WAS A |
| | REASONABLE NUMBER OF PEOPLE FOR A 6 BEDROOM HOUSE WITH |
| | 2 MASTER BEDROOMS. THAT'S WHY I DIDN'T SAY ANYTHING |
| | ABOUT THE NUMBER OF PEOPLE CONSIDERED ON THE ENERGY |
| | CALCULATIONS. REVISED ENERGY CALCULATIONS ARE NOW |
| | SHOWING 4 PEOPLE IN THE GREAT ROOM. THIS DOESN'T LOOK |
| | CORRECT SINCE THE NUMBER OF PEOPLE ARE ALREADY COUNTED |
| | IN THE BEDROOMS. REVISE AS REQUIRED. NOTE: NUMBER OF |
| | PEOPLE MAY AFFECT THE SIZING OF THE A/C EQUIPMENT. MAY |
| | BE THAT'S WHY THE EQUIPMENT SIZING CALCULATIONS ARE |
| | USING 12 PEOPLE INSTEAD OF 8. THE ENERGY CODE DOESN'T |
| | ALLOW TO USE FACTORS THAT AFFECT THE EQUIPMENT SIZING. |
| | SEE SEC. R403.6.1 FBC-ENERGY CONSERVATION. REVISE AS |
| | REQUIRED USING THE CORRECT NUMBER OF PEOPLE. |
| | |
| | 2- REVISE A/C PLAN TO REFLECT THE NEW EQUIPMENT. |
| | NOTE: DON'T FORGET TO HAVE THE NAME AND SIGNATURE OF |
| | THE A/C CONTRACTOR RESPONSIBLE FOR THE A/C DESIGN. |