| Plan Review Notes For Permit 17090467 |
| Permit Number |
17090467 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2018-01-29 13:36:51 | 01/29/18 | | | RECEIVED REVISED CALCULATIONS FROM NICOLE BLACKWELL | | | FROM QUICKCALCS. | | | (ENERGY CALCULATIONS AND EQUIPMENT SIZING | | | CALCULATIONS). JG. | | | | | | | | | ENERGY CALCULATIONS REVISION COURTESY REVIEW; | | | 1- THE PERMIT OFFICE IS CITY OF WEST PALM BEACH NOT | | | CITY OF PALM BEACH. (PALM BEACH IS ANOTHER | | | MUNICIPALITY) | | | 2- OWNER OR LEGAL AGENT TO SIGN AND DATE ENERGY | | | CALCULATIONS. | | | 3- BUILDER TO COMPLETE THE EPL CARD. | | | | | | NEW COMMENT: | | | 1- NUMBER OF PEOPLE WAS CHANGED FROM 8 PEOPLE TO 12 | | | PEOPLE. 8 PEOPLE WAS A REASONABLE NUMBER OF PEOPLE FOR | | | A 6 BEDROOM HOUSE WITH 2 MASTER BEDROOMS. THAT'S WHY I | | | DIDN'T SAY ANYTHING ABOUT THE NUMBER OF PEOPLE | | | CONSIDERED ON THE ENERGY CALCULATIONS. REVISED ENERGY | | | CALCULATIONS ARE NOW SHOWING 4 PEOPLE IN THE GREAT | | | ROOM. THIS DOESN'T LOOK CORRECT SINCE THE NUMBER OF | | | PEOPLE ARE ALREADY COUNTED IN THE BEDROOMS. REVISE AS | | | REQUIRED. NOTE: NUMBER OF PEOPLE MAY AFFECT THE SIZING | | | OF THE A/C EQUIPMENT. MAY BE THAT'S WHY THE EQUIPMENT | | | SIZING CALCULATIONS ARE USING 12 PEOPLE INSTEAD OF 8. | | | THE ENERGY CODE DOESN'T ALLOW TO USE FACTORS THAT | | | AFFECT THE EQUIPMENT SIZING. SEE SEC. R403.6.1 | | | FBC-ENERGY CONSERVATION. REVISE AS REQUIRED USING THE | | | CORRECT NUMBER OF PEOPLE. EQUIPMENT SIZING CALCULATIONS | | | WILL NEED TO BE REVISED AS WELL. |
|