| Plan Review Notes For Permit 17090467 |
| Permit Number |
17090467 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2018-01-26 17:13:12 | RECEIVED E-MAIL FROM NICOLE BLACKWELL FROM QUICKCALCS. | | | NEW ENERGY CALCULATIONS AND EQUIPMENT SIZING | | | CALCULATIONS. JG. | | | | | | | | | EQUIPMENT SIZING CALCULATIONS COURTESY REVIEW: | | | 1- CORRECT ADDRESS IS 5401 S. OLIVE AVE NOT 541 | | | 2- TYPICALLY, THE SAME PERSON DOING THE ENERGY | | | CALCULATIONS TRANSFER THE INFORMATION TO DO THE | | | EQUIPMENT SIZING CALCULATIONS. ENERGY CALCULATIONS NEED | | | TO BE CORRECTED TO THE ACTUAL ORIENTATION OF THE | | | BUILDING. THEREFORE, EQUIPMENT SIZING CALCULATIONS NEED | | | TO BE REVISED ALSO REFLECTING THE ACTUAL ORIENTATION OF | | | THE BUILDING. | | | 3- THE NUMBER OF PEOPLE SHOWN ON THE EQUIPMENT SIZING | | | CALCULATIONS DOESN'T MATCH THE NUMBER OF PEOPLE SHOWN | | | ON THE ENERGY CALCULATIONS. REVISE AS REQUIRED. | | | 4- REVISE A/C PLAN TO REFLECT THE NEW EQUIPMENT. |
|