| 2017-11-15 12:03:11 | RESIDENTIAL (R3) REVISION SECOND MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | 1- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED: PROVIDE |
| | COMPLETE EQUIPMENT SIZING CALCULATIONS "BASED ON |
| | BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE |
| | BUILDING" AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | NOTE: IT LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS |
| | WERE DONE BY THE SAME PERSON WHO DID THE ENERGY |
| | CALCULATIONS. THE ENERGY CALCULATIONS NEED TO BE |
| | REVISED. SEE BUILDING REVIEW COMMENTS ON ITEM #1 AND |
| | REVISE A/C EQUIPMENT SIZING CALCULATIONS AS REQUIRED. |
| | |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SAME |
| | CALCULATIONS DATED AUGUST 25TH 2017 WERE SUBMITTED. |
| | AND, ONLY THE SUMMARY PAGES WERE SUBMITTED. NEED THE |
| | COMPLETE EQUIPMENT SIZING CALCULATIONS. IN ADDITION, |
| | THE ENERGY CALCULATIONS WERE REVISED ON 10/23/17 |
| | SHOWING THE ACTUAL ORIENTATION OF THE BUILDING, BUT THE |
| | EQUIPMENT SIZING CALCULATIONS WERE NOT REVISED. |
| | PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED ON |
| | THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED BY |
| | SEC. R403.6.1 FBC-ENERGY CONSERVATION. |
| | |
| | |