| 2017-09-26 14:30:41 | RESIDENTIAL (R3) REVISION BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | 1- REVISE ENERGY CALCULATIONS: |
| | A) CALCULATIONS NEED TO BE DONE ON THE CORRECT |
| | ORIENTATION OF THE BUILDING. SEE SURVEY AND PLANS AND |
| | REVISE WALLS AND WINDOWS INFORMATION AS REQUIRED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | NOTE: CHECK OVERHANG DEPTH AND SEPARATION. MET |
| | CONTRACTOR ON 10/10/17. |
| | |
| | B) WALL TYPES ARE INCORRECT. THERE ARE NO INTERIOR |
| | STEEL PARTITIONS SEPARATING A/C SPACE FROM NON A/C |
| | SPACE. PLANS SPECIFY WOOD FRAMED WALLS. SEE PLANS AND |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | C) REVISE THE DOORS INFORMATION SHOWN ON PAGE 3 OF 5. |
| | WHERE ARE THE 16'-0" X 8'-0" INSULATED DOORS?. SEE |
| | PLANS AND PRODUCT APPROVALS SUBMITTED. NOTE: DOORS WITH |
| | GLAZING NEED TO BE CONSIDERED IN THE WINDOWS AREA AS |
| | REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION. |
| | REVISE AS REQUIRED. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | |
| | 2- A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED: PROVIDE |
| | COMPLETE EQUIPMENT SIZING CALCULATIONS "BASED ON |
| | BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE |
| | BUILDING" AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | NOTE: IT LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS |
| | WERE DONE BY THE SAME PERSON WHO DID THE ENERGY |
| | CALCULATIONS. THE ENERGY CALCULATIONS NEED TO BE |
| | REVISED. SEE COMMENTS ON ITEM #1 ABOVE AND REVISE A/C |
| | EQUIPMENT SIZING CALCULATIONS AS REQUIRED. |
| | |
| | 3- TRUSS PACKAGE SUBMITTED: |
| | A) REVISE DESIGN LOADS TO MATCH DESIGN CRITERIA |
| | SPECIFIED BY THE ENGINEER OF RECORD ON SHEET 2.1. NOTE: |
| | KEEP IN MIND THAT FINISH ROOF IS CONCRETE TILE. |
| | SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) TRUSS LAYOUT AND ALL INDIVIDUAL TRUSS DRAWINGS NEED |
| | TO BE SIGNED AND SEALED AND HAVE THE TRUSS ENGINEER |
| | INFORMATION IN ALL DRAWINGS AS REQUIRED BY FAC |
| | 61G15-31.003. |
| | NOTE: TRUSS LAYOUT WAS NOT SUBMITTED AT THIS TIME. NEED |
| | TO SUBMIT PROPERLY SIGNED AND SEALED TRUSS LAYOUT. |
| | |
| | C) REVISED TRUSS PACKAGE TO BE APPROVED IN WRITING BY |
| | THE ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS |
| | OFFICE. SEC. 107.3.4.2 CITY AMENDMENTS. |
| | |
| | NOTE: |
| | THE REVISION FEE OF $207.00 WAS NOT PAID. NEED TO PAY |
| | FEE NOW BEFORE ANY ADDITIONAL REVIEW IS PERFORMED. |
| | ADDITIONAL FEES WILL BE CHARGED ON EVERY RE-SUBMITTALS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |