| 2017-09-25 13:42:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PICTURE AND SITE SURVEY DO NOT MATCH. |
| | IT APPEARS THE TANKS ARE LOCATED ON OPPISITE SIDES OF |
| | THE OTHER. |
| | |
| | WHICH IS CORRECT? |
| | |
| | |
| | |
| | 2) IT APPEARS THAT THE TANKS ARE PROPOSED TO UNDERNEATH |
| | A POWER LINE. |
| | |
| | PER NFPA 58, INSTALLATION OF LP-GAS SYSTEMS |
| | |
| | 6.4.5.12 AN ABOVEGROUND LP-GAS CONTAINER AND ANY OF ITS |
| | PARTS SHALL NOT BE LOCATED WITHIN 6 FT (1.8 M) OF A |
| | VERTICAL PLANE BENEATH OVERHEAD ELECTRIC POWER LINES |
| | THAT ARE OVER 600 VOLTS, NOMINAL. |
| | |
| | |
| | PLEASE PROVIDE A NOTE INDICATING COMPLIANCE OR MOVE THE |
| | TANK. |
| | |
| | |
| | |
| | 3) THERE APPEARS TO BE UNDERGROUND PIPING PROPOSED. |
| | THERE IS LIMITED UNDERGROUND INFORMATION SUBMITTED. |
| | |
| | PER NFPA 58, INSTALLATION OF LP-GAS SYSTEMS |
| | |
| | 6.9.3.12 BURIED METALLIC PIPE AND TUBING SHALL BE |
| | INSTALLED UNDERGROUND WITH A MINIMUM 12 IN. (300 MM) OF |
| | COVER. THE MINIMUM COVER SHALL BE INCREASED TO 18 IN. |
| | (460 MM) IF EXTERNAL DAMAGE TO THE PIPE OR TUBING FROM |
| | EXTERNAL FORCES IS LIKELY TO RESULT. IF A MINIMUM 12 |
| | IN. (300 MM) OF COVER CANNOT BE MAINTAINED, THE PIPING |
| | SHALL BE INSTALLED IN CONDUIT OR SHALL BE BRIDGED |
| | (SHIELDED). |
| | 6.9.3.13 WHERE UNDERGROUND PIPING IS BENEATH DRIVEWAYS, |
| | ROADS, OR STREETS, POSSIBLE DAMAGE BY VEHICLES SHALL BE |
| | TAKEN INTO ACCOUNT. |
| | 6.9.3.14 UNDERGROUND METALLIC PIPING SHALL BE PROTECTED |
| | AGAINST CORROSION AS WARRANTED BY SOIL CONDITIONS. (SEE |
| | SECTION 6.16.) |
| | 6.9.3.15 LP-GAS PIPING SHALL NOT BE USED AS A GROUNDING |
| | ELECTRODE. |
| | 6.9.3.16 UNDERGROUND METALLIC PIPING, TUBING, OR BOTH |
| | THAT CONVEY LP-GAS FROM A GAS STORAGE CONTAINER SHALL |
| | BE PROVIDED WITH DIELECTRIC FITTINGS AT THE BUILDING TO |
| | ELECTRICALLY ISOLATE IT FROM THE ABOVEGROUND PORTION OF |
| | THE FIXED PIPING SYSTEM THAT ENTERS A BUILDING. SUCH |
| | DIELECTRIC FITTINGS SHALL BE INSTALLED ABOVE GROUND AND |
| | OUTDOORS. |
| | |
| | PLEASE PROVIDE GREATER DETAIL AND A NOTE OF COMPLIANCE. |
| | |
| | |
| | |
| | 4) THE PROPOSED TANKS APPEAR TO BE NEAR A VEHICLE |
| | TRAFFIC LANE. THE TANKS SHALL BE PROVIDED WITH |
| | PROTECTION AGAINST UNINTENDED VEHICLE CONTACT, I.E |
| | POLLARDS. |
| | |
| | PLEASE PROVIDE PROTECTION FROM VEHICLE CONTACT. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |