| Notes |
| Date |
Text |
| 2017-10-02 10:38:09 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17090437 | | | 10/2/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REVIEW BUILDING COMMENT #3 REGARDING EXTERIOR | | | EQUIPMENT IN A FLOOD HAZARD AREA AND PROVIDE A SITE | | | PLAN THAT SHOWS THE LOCATION OF THE AC CONDENSE. REFER | | | TO SECTION 301.16: | | | | | | [B] 301.16 FLOOD HAZARD. | | | FOR STRUCTURES LOCATED IN FLOOD HAZARD AREAS, | | | MECHANICAL SYSTEMS, EQUIPMENT AND APPLIANCES SHALL BE | | | LOCATED AT OR ABOVE THE ELEVATION REQUIRED BY SECTION | | | 1612 OF THE FLORIDA BUILDING CODE, BUILDING FOR | | | UTILITIES AND ATTENDANT EQUIPMENT. | | | | | | EXCEPTION: MECHANICAL SYSTEMS, EQUIPMENT AND APPLIANCES | | | ARE PERMITTED TO BE LOCATED BELOW THE ELEVATION | | | REQUIRED BY SECTION 1612 OF THE OF THE FLORIDA BUILDING | | | CODE, BUILDING FOR UTILITIES AND ATTENDANT EQUIPMENT | | | PROVIDED THAT THEY ARE DESIGNED AND INSTALLED TO | | | PREVENT WATER FROM ENTERING OR ACCUMULATING WITHIN THE | | | COMPONENTS AND TO RESIST HYDROSTATIC AND HYDRODYNAMIC | | | LOADS AND STRESSES, INCLUDING THE EFFECTS OF BUOYANCY, | | | DURING THE OCCURRENCE OF FLOODING UP TO SUCH ELEVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|