| 2017-11-30 19:15:18 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENGINEER NEEDS TO SPECIFY THE REQUIRED EMBEDMENT | | | DEPTH OF THE ANCHORS ON THE TIE DOWN SCHEDULE DRAWING | | | OR PROVIDE THE MANUFACTURER'S SPECIFICATIONS THAT | | | SPECIFY THE REQUIRED EMBED DEPTHS. FBC-R301.1 | | | | | | 2) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS | | | OR PRODUCT APPROVALS FOR THE EARTH AND CONCRETE | | | ANCHORS. FBC 107.2.1 |
|