| 2017-10-02 14:37:16 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW ON ENLARGED PLAN GRAB BARS SHALL COMPLY WITH |
| | FBC ACC 608.3.2 WHERE A SEAT IS NOT PROVIDED IN |
| | STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB BARS |
| | SHALL BE PROVIDED ON THREE WALLS. GRAB BARS SHALL BE |
| | INSTALLED 6 INCHES (150 MM) MAXIMUM FROM ADJACENT |
| | WALLS. |
| | |
| | 2. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE TO FINISHED FLOOR. PER FBC ACC 609.4 |
| | |
| | 3. DIMENSION MISSING DETAIL #6 SHT. A3 SHALL COMPLY |
| | WITH FBC ACC 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 4. SHOW COMPLIANCE FBC ACC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 5. LAV SHALL COMPLY WITH FBC PL 416.5 TEMPERED WATER |
| | FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |