| 2017-09-27 15:01:15 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) SURVEY OF THE PROPERTY IS REQUIRED. PLEASE SUBMIT. | | | | | | 2.) REVIEW OF PROPOSED PERIMETER LANDSCAPING SHALL BE | | | SUBMITTED UNDER A SEPARATE PERMIT APPLICATION. PLEASE | | | NOTE THAT THE LANDSCAPE PLAN SHALL BE SIGNED, DATED AND | | | SEALED BY A FLORIDA REGISTERED LANDSCAPE ARCHITECT. | | | | | | 3.) HOW TALL IS THE PROPOSED FENCE AROUND THE LIFT | | | STATION? PLEASE PROVIDE HEIGHT AND DETAILS (I.E. CHAIN | | | LINK FENCE, ETC.). | | | | | | 4.) GENERATOR PAD SHALL BE SETBACK AT LEAST 5 FT. FROM | | | THE PROPERTY LINE. PLEASE PROVIDE DIMENSIONS. | | | | | | | | | NOTES: | | | | | | * ZONE: ROS | | | | | | * SPOKE TO SKENNEDY ON 9/1/17. SEPARATE FENCE PERMIT IS | | | NOT REQUIRED FOR LIFT STATION. | | | | | | * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|