Plan Review Notes
Plan Review Notes For Permit 17090365
Permit Number 17090365
Review Stop Z
Sequence Number 1
Notes
Date Text
2017-09-27 15:01:15** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SURVEY OF THE PROPERTY IS REQUIRED. PLEASE SUBMIT.
  
 2.) REVIEW OF PROPOSED PERIMETER LANDSCAPING SHALL BE
 SUBMITTED UNDER A SEPARATE PERMIT APPLICATION. PLEASE
 NOTE THAT THE LANDSCAPE PLAN SHALL BE SIGNED, DATED AND
 SEALED BY A FLORIDA REGISTERED LANDSCAPE ARCHITECT.
  
 3.) HOW TALL IS THE PROPOSED FENCE AROUND THE LIFT
 STATION? PLEASE PROVIDE HEIGHT AND DETAILS (I.E. CHAIN
 LINK FENCE, ETC.).
  
 4.) GENERATOR PAD SHALL BE SETBACK AT LEAST 5 FT. FROM
 THE PROPERTY LINE. PLEASE PROVIDE DIMENSIONS.
  
  
 NOTES:
  
 * ZONE: ROS
  
 * SPOKE TO SKENNEDY ON 9/1/17. SEPARATE FENCE PERMIT IS
 NOT REQUIRED FOR LIFT STATION.
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  